| Date |
Text |
| 2019-01-22 14:37:19 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. BASED ON THE SQUARE FOOTAGE AND ESTIMATED OCCUPANT |
| | LOAD, THIS STRUCTURE SHALL COMPLY WITH THE REQUIREMENTS |
| | OF FS 553,79 "THRESHOLD BUILDINGS:.PLEAS SEE COMMENTS |
| | UNDER THRESHOLD REVIEW. |
| | |
| | 2. THRESHOLD BUILDING |
| | CONFORMING TO CHAPTER 553 FLORIDA STATUTES, |
| | CHAPTER 468, PART XII, FLORIDA STATUTES |
| | AND THE FLORIDA BUILDING CODE AS AMENDED BY CITY OF |
| | WEST PALM BEACH |
| | |
| | 3. PROVIDE A LIFE SAFETY PLAN. |
| | A) STATE OCCUPANT LOAD. |
| | B) IDENTIFY MEANS OF EGRESS. |
| | C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO EXIT. |
| | NOTE: AN ADDITIONAL EXIT MAY BE REQUIRED. THIS EXIT |
| | SHALL COMPLY WITH THE REQUIREMENTS OF AN ACCESSIBLE |
| | EGRESS EXIT. |
| | |
| | 4. ) IDENTIFY ACCESSIBLE ROUTE ON SITE PLAN. IDENTIFY |
| | PATH OF TRAVEL FROM DROP-OFF AREA TO ACCESSIBLE |
| | ENTRANCE ON SITE PLAN. |
| | |
| | 5. PROVIDE DETAIL OF FLOORING TO BE USED. |
| | |
| | 6. PROVIDE DETAIL OF ACCESSIBLE RAMP. RAMPS SHALL |
| | COMPLY WITH FBC ACCESSIBLITY SECTION 405. |
| | |
| | 7. PLUMBING FIXTURES SHALL COMPLY WITH FBC TABLE |
| | 2902.1. |
| | 7A. BASED ON THE ESTIMATED OCCUPANT LOAD OF 422 SEATS |
| | THERE SHALL BE 3 WATER CLOSETS FOR THE MEN'S ROOM AND 6 |
| | WATER CLOSETS FOR THE WOMENS ROOM. |
| | |
| | 8. ACCESSIBLE RESTROOMS SHALL COMPLY WITH FBC |
| | ACCESSIBILITY CODE SECTION 213.3.1 AND SHALL ALSO |
| | COMPLY WITH SECTION 604.2 (WHEEL CHAIR ACCESSIBLE |
| | COMPARTMENTS). |
| | 8A. BASED ON THE INDIVIDUAL NUMBER OF FIXTURES FOR THE |
| | MEN'S AND WOMEN'S ROOMS THERE SHALL BE ONE ACCESSIBLE |
| | COMPARTMENT FOR THE MEN AND ONE ACCESSIBLE COMPARTMENT |
| | FOR THE WOMEN. THESE COMPARTMENTS SHALL ALSO COMPLY |
| | WITH SECTION 604.2. |
| | 8B. WE HAVE REVIEWED THE REQUIREMENTS FOR ACCESSIBLE |
| | FACILITIES BASED ON FBC P CHPT. 403.1.3 (POTTY PARITY) |
| | AND FOUND NO ADDITIONAL FIXTURES ARE REQUIRED FOR THE |
| | WOMEN'S RESTROOM. |
| | |
| | TEMPORARY MEMBRANE STRUCTURES |
| | (TENTS) FBC CHPT. 31 |
| | |
| | 3103.1 CONFORMANCE. |
| | 1. PROVIDE STATEMENT FOR DATE OF ASSEMBLY AND DATE OF |
| | REMOVAL. |
| | 2. PROVIDE SITE PLAN. SHOW LOCATION OF PROPOSED |
| | STRUCTURE AND DISTANCE TO PROPERTY LINES AND OTHER |
| | STRUCTURES PER FBC CHPT. 6, SEC. 602. |
| | 3. CONFORMANCE REQUIREMENTS PER SEC. 3103.1.1 |
| | TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| | STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| | ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| | REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| | HEALTH, SAFETY AND GENERAL WELFARE. |
| | A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? SUPPLIER TO |
| | PROVIDE CERTIFIED REPORT. |
| | B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER |
| | NFPA 701. |
| | C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN |
| | REQUIRED. |
| | 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN |
| | A) STATE OCCUPANT LOAD. |
| | B) IDENTIFY MEANS OF EGRESS. |
| | C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO |
| | EXIT. |
| | D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE |
| | PLAN |
| | E. LIGHT 1) OPEN SIDES ? N/A |
| | 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE |
| | F. VENTILATION 1) OPEN SIDES ? N/A |
| | 2) CLOSED SIDES ? PER SEC. 1203 |
| | G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES |
| | ON SITE PLAN |
| | 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |