Plan Review Notes
Plan Review Notes For Permit 19010721
Permit Number 19010721
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-22 14:37:19BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BASED ON THE SQUARE FOOTAGE AND ESTIMATED OCCUPANT
 LOAD, THIS STRUCTURE SHALL COMPLY WITH THE REQUIREMENTS
 OF FS 553,79 "THRESHOLD BUILDINGS:.PLEAS SEE COMMENTS
 UNDER THRESHOLD REVIEW.
  
 2. THRESHOLD BUILDING
 CONFORMING TO CHAPTER 553 FLORIDA STATUTES,
 CHAPTER 468, PART XII, FLORIDA STATUTES
 AND THE FLORIDA BUILDING CODE AS AMENDED BY CITY OF
 WEST PALM BEACH
  
 3. PROVIDE A LIFE SAFETY PLAN.
 A) STATE OCCUPANT LOAD.
 B) IDENTIFY MEANS OF EGRESS.
 C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO EXIT.
 NOTE: AN ADDITIONAL EXIT MAY BE REQUIRED. THIS EXIT
 SHALL COMPLY WITH THE REQUIREMENTS OF AN ACCESSIBLE
 EGRESS EXIT.
  
 4. ) IDENTIFY ACCESSIBLE ROUTE ON SITE PLAN. IDENTIFY
 PATH OF TRAVEL FROM DROP-OFF AREA TO ACCESSIBLE
 ENTRANCE ON SITE PLAN.
  
 5. PROVIDE DETAIL OF FLOORING TO BE USED.
  
 6. PROVIDE DETAIL OF ACCESSIBLE RAMP. RAMPS SHALL
 COMPLY WITH FBC ACCESSIBLITY SECTION 405.
  
 7. PLUMBING FIXTURES SHALL COMPLY WITH FBC TABLE
 2902.1.
 7A. BASED ON THE ESTIMATED OCCUPANT LOAD OF 422 SEATS
 THERE SHALL BE 3 WATER CLOSETS FOR THE MEN'S ROOM AND 6
 WATER CLOSETS FOR THE WOMENS ROOM.
  
 8. ACCESSIBLE RESTROOMS SHALL COMPLY WITH FBC
 ACCESSIBILITY CODE SECTION 213.3.1 AND SHALL ALSO
 COMPLY WITH SECTION 604.2 (WHEEL CHAIR ACCESSIBLE
 COMPARTMENTS).
 8A. BASED ON THE INDIVIDUAL NUMBER OF FIXTURES FOR THE
 MEN'S AND WOMEN'S ROOMS THERE SHALL BE ONE ACCESSIBLE
 COMPARTMENT FOR THE MEN AND ONE ACCESSIBLE COMPARTMENT
 FOR THE WOMEN. THESE COMPARTMENTS SHALL ALSO COMPLY
 WITH SECTION 604.2.
 8B. WE HAVE REVIEWED THE REQUIREMENTS FOR ACCESSIBLE
 FACILITIES BASED ON FBC P CHPT. 403.1.3 (POTTY PARITY)
 AND FOUND NO ADDITIONAL FIXTURES ARE REQUIRED FOR THE
 WOMEN'S RESTROOM.
  
 TEMPORARY MEMBRANE STRUCTURES
 (TENTS) FBC CHPT. 31
  
 3103.1 CONFORMANCE.
 1. PROVIDE STATEMENT FOR DATE OF ASSEMBLY AND DATE OF
 REMOVAL.
 2. PROVIDE SITE PLAN. SHOW LOCATION OF PROPOSED
 STRUCTURE AND DISTANCE TO PROPERTY LINES AND OTHER
 STRUCTURES PER FBC CHPT. 6, SEC. 602.
 3. CONFORMANCE REQUIREMENTS PER SEC. 3103.1.1
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? SUPPLIER TO
 PROVIDE CERTIFIED REPORT.
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701.
 C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN
 REQUIRED.
  2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN
  A) STATE OCCUPANT LOAD.
  B) IDENTIFY MEANS OF EGRESS.
  C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO
 EXIT.
  D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE
 PLAN
  E. LIGHT 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
  F. VENTILATION 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1203
  G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES
 ON SITE PLAN
  2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved