| 2019-01-31 15:53:25 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. THE LOAD CALCULATION PROVIDED DOES |
| | NOT ACCOUNT FOR ALL LOADS SHOWN IN PANEL SCHEDULE. NO |
| | LOAD CALCULATION IS PROVIDED FOR PANEL B, BUT IT |
| | APPEARS THAT THIS PANEL WILL BE OVERLOADED. DEMAND |
| | FACTORS ARE NOT PERMITTED TO BE USED ON FEEDERS LESS |
| | THAN 100 AMPS. THE LOAD IN PANEL A SHOWN FOR PANEL B IS |
| | MUCH LOWER THAN WHAT IS INCLUDED IN PANEL B. NEC 215.2, |
| | 220, 408.30; FBC RE E3602.2 |
| | 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| | FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| | 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 4. IF NEW ADDITIONS TO LOAD REQUIRE AN INCREASE IN THE |
| | SERVICE SIZE, PROVIDE AIC RATING OF SERVICE DISCONNECT |
| | AND ANY PANELS. NEC 110.3, 110.9; FBC RE E3606.3 |
| | 5. IF NEW ADDITIONS TO LOAD REQUIRE AN INCREASE IN THE |
| | SERVICE SIZE, PROVIDE AVAILABLE SHORT CIRCUIT |
| | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE |
| | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| | CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC |
| | RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, |
| | 110.10; FBC RE E3606.3 |
| | 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |