| Plan Review Notes For Permit 19010673 |
| Permit Number |
19010673 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-04 08:34:05 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF GENERATOR PAD CONSTRUCTION | | | DETAILS WITH GENERATOR TO PAD ANCHORING DETAILS. FBC-R | | | 301.2.1 | | | | | | 2) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA. THE GENERATOR IS REQUIRED TO BE LOCATED AT OR | | | ABOVE THE SAME ELEVATION AS THE FINISH FLOOR OF THE | | | RESIDENCE. FBC-R322.1.6 |
|