Plan Review Notes
Plan Review Notes For Permit 19010660
Permit Number 19010660
Review Stop P
Sequence Number 3
Notes
Date Text
2019-05-15 10:13:09PLUMBING PROVISO:
  
 SHALL COMPLY PRIOR TO 1ST ROUGH INSPECTION.
  
 1. PROVIDE FLOOR PLAN AND ISOMETRIC DRAWING FOR GREASE
 INTERCEPTOR AND CONNECTED FIXTURES. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 2. PROVIDE INSTALLATION GUIDE FOR GREASE INTERCEPTOR.
 FBC PL 1002.4.1
  
 3. MOVABLE SINK SYSTEMS SHALL COMPLY WITH ASME
 A112.19.12. THE MANUFACTURE SPECIFICATIONS PROVIDED FOR
 THE HAND SINK AT THE BAR DO NOT COMPLY PLEASE PROVIDE
 SPECIFICATIONS THAT SHOW COMPLIANCE OR A SINK SYSTEM
 THAT DOES COMPLY. PER FBC PL 418.3
  
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]