| 2019-04-16 09:48:00 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE SIZING CALCULATIONS FOR GREASE INTERCEPTOR |
| | INCLUDE ALL FIXTURE REQUIRED TO DISCHARGE THROUGH |
| | INTERCEPTOR 3 COMPARTMENT SINK MOP SINK ANY OTHER SINK |
| | RECEIVING GREASE WASTE. PER FBC PL 1003.2 |
| | |
| | 2. PLACE NOTE ON THE PLAN AN AS-BUILD DRAWING OF PIPING |
| | FOR GREASE INTERCEPTOR AND CONNECTED SINKS. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 3. PROVIDE MANUFACTURE SPECIFICATIONS OF SELF CONTAINED |
| | SINK AT BAR. PER WPB AMEND TO FBC 107.2.1 AND SHALL |
| | COMPLY WITH FBC PL 418.3 MOVABLE SINK SYSTEMS.MOVABLE |
| | SINK SYSTEMS SHALL COMPLY WITH ASME A112.19.12. |
| | |
| | 4. SEE COMMENTS FROM BUILDING AND PROVIDE COMPLETE |
| | DIMENSIONS OF THE BATHROOMS TO VERIFY COMPLIANCE WITH |
| | FBC ACC CH 6 PER FBC EX 806.1 GENERAL.A BUILDING, |
| | FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH |
| | THE PROVISIONS OF THE FLORIDA BUILDING CODE, |
| | ACCESSIBILITY. |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |