Plan Review Notes
Plan Review Notes For Permit 19010660
Permit Number 19010660
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-16 09:48:001ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SIZING CALCULATIONS FOR GREASE INTERCEPTOR
 INCLUDE ALL FIXTURE REQUIRED TO DISCHARGE THROUGH
 INTERCEPTOR 3 COMPARTMENT SINK MOP SINK ANY OTHER SINK
 RECEIVING GREASE WASTE. PER FBC PL 1003.2
  
 2. PLACE NOTE ON THE PLAN AN AS-BUILD DRAWING OF PIPING
 FOR GREASE INTERCEPTOR AND CONNECTED SINKS. PER WPB
 AMEND TO FBC 107.2.1
  
 3. PROVIDE MANUFACTURE SPECIFICATIONS OF SELF CONTAINED
 SINK AT BAR. PER WPB AMEND TO FBC 107.2.1 AND SHALL
 COMPLY WITH FBC PL 418.3 MOVABLE SINK SYSTEMS.MOVABLE
 SINK SYSTEMS SHALL COMPLY WITH ASME A112.19.12.
  
 4. SEE COMMENTS FROM BUILDING AND PROVIDE COMPLETE
 DIMENSIONS OF THE BATHROOMS TO VERIFY COMPLIANCE WITH
 FBC ACC CH 6 PER FBC EX 806.1 GENERAL.A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  