| 2019-01-25 10:00:25 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19010660 |
| | REVIEWED: JANUARY 25, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1. 107.2.1 FBC[B] INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. THE SHEETS WERE UPLOADED AT 11X17 WITH A 1/4 |
| | INCH SCALE INDICATED. TYPICALLY THESE SHEETS WOULD BE |
| | 24X36 AND SHOULD BE PRINTED OUT AT THAT SIZE FOR |
| | INSPECTORS TO USE AT THE SITE. |
| | A. PLEASE UPDATE PAPER SIZE THAT THE SCALE MATCHES. I |
| | CANNOT SCALE OFF OF THE PROVIDED SHEETS. |
| | B. DIMENSION CLEAR SPACE IN BAR AREA AROUND PREP TABLE. |
| | THIS TABLE APPEARS TO RESTRICT EGRESS FROM THAT AREA. |
| | C. PROVIDE DETAIL OF BAR CONSTRUCTION AND SPACE |
| | PROVIDED BELOW. |
| | D. SHOW CLEAR SPACE AT ADA BATHROOMS. |
| | |
| | 1210.2.2 FBC[B] WALLS AND PARTITIONS. WALLS AND |
| | PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE |
| | FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| | MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS |
| | NOT ADVERSELY AFFECTED BY MOISTURE. |
| | A. WHAT IS PROVIDED FOR WALL FINISH IN BATHROOMS AND |
| | ARE ANY OTHER FINISHES BEING PROVIDED? |
| | B. IS THERE AND DEMO TO SHOW OR EXISTING CONDITIONS? |
| | THE DOUBLE DOORS OPENING TO EXTERIOS SHOW ONE AS |
| | DASHED. IS THERE ANY WORK IN THIS AREA. IF NEW DOOR |
| | PLEASE PROVIDE PRODUCT APPROVAL, OR INDICATE THAT IT |
| | WILL BE A DEFERRED SUBMITTAL. |
| | |
| | 2. 1006.2.1 FBC TABLE[B] SHEET LS102 MAXIMUM COMMON |
| | PATH OF EGRESS TRAVEL DISTANCE. |
| | -PLEASE STATE THE MAXIMUM COMMON PATH FROM TABLE |
| | 1006.2.1. SHOW THE FULL DISTANCE OF TRAVEL TO THE |
| | EXTERIOR OF BUILDING SINCE THE EXIT STAIRS FROM |
| | MEZZANINE ARE NOT ENCLOSED. |
| | |
| | 3. 505.2.1 FBC[B] AREA LIMITATION. THE AGGREGATE AREA |
| | OF A MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL BE NOT |
| | GREATER THAN ONE-THIRD OF THE FLOOR AREA OF THAT ROOM |
| | OR SPACE IN WHICH THEY ARE LOCATED. |
| | THE CURRENT MEZZANINE DOESN?T MEET THE SIZE |
| | REQUIREMENTS FOR A MEZZANINE. THIS SHOULD BE CONSIDERED |
| | A 2 ND FLOOR. |
| | THE FLOOR OPENING IS ALLOWED PER 712.1.9 TWO-STORY |
| | OPENINGS. |
| | -PLEASE RENAME THIS LEVEL AND INCLUDE THE AREA IN AREA |
| | DATA SHEET G001. |
| | |
| | 4. 226.1 FBC[A] THE ACCESSIBILITY CODE REQUIRES 0.05 % |
| | OF ALL SEATING TO BE ACCESSIBLE. WHERE DINING SURFACES |
| | ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT |
| | LEAST 0.05 PERCENT OF THE SEATING SPACES AND STANDING |
| | SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902. |
| | -SHOW ON PLANS 0.05% OF SEATING TO COMPLY WITH 226.1 |
| | AND 902 FOR THE BAR SEATING. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |