| Plan Review Notes For Permit 19010634 |
| Permit Number |
19010634 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-04 13:45:59 | PLAN DENIED | | | 1) PROVIDE ENERGY CALCULATION FOR A/C NONE PROVIDE. | | | PER SECTION C103.2 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. 2017 FLORIDA ENERGY CODE. | | | 2) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS | | | FOR MAKE UP AIR. 2017 FLORIDA ENERGY CODE. | | | 3) GENERAL NOTE # 7 PAGE M2.1 IS INDICATING | | | RTU 1 AND 2 TO BE CHANGED OUT. THIS APPEARS | | | TO BE A MISPRINT. THE POSSIBLE INTENT WAS FOR RTU | | | NUMBER 3 AND 7 TO BE CHANGED OUT. PLEASE | | | CALCIFY. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|