2019-03-04 13:45:59PLAN DENIED
 1) PROVIDE ENERGY CALCULATION FOR A/C NONE PROVIDE.
 PER SECTION C103.2 INFORMATION ON CONSTRUCTION
 DOCUMENTS. 2017 FLORIDA ENERGY CODE.
 2) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS
 FOR MAKE UP AIR. 2017 FLORIDA ENERGY CODE.
 3) GENERAL NOTE # 7 PAGE M2.1 IS INDICATING
 RTU 1 AND 2 TO BE CHANGED OUT. THIS APPEARS
 TO BE A MISPRINT. THE POSSIBLE INTENT WAS FOR RTU
 NUMBER 3 AND 7 TO BE CHANGED OUT. PLEASE
 CALCIFY.
  