Plan Review Notes
Plan Review Notes For Permit 19010634
Permit Number 19010634
Review Stop B
Sequence Number 1
Notes
Date Text
2019-02-21 10:26:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:19010634
 ADD: 5133 TYLERLAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ??????????
 E-MAIL: [email protected] CONTACT: DAVID SOLANO
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB. 21/ 2019
 ACTION: DENIED
  
 1) THE TITLE SHEET 001_T101 LIST THE BUILDING DESIGN
 WITH THE 2017 FLORIDA BUILDING CODE- BUILDING AND THE
 EXISTING BUILDING CODE BUT DOES NOT LIST THE COMPLIANCE
 METHOD USED TO DEVELOP THE PLANS UNDER THE EXISTING
 BUILDING CODE.
 2017 FBC-EXISTING BUILDING CODE 301.1. THE ALTERATION
 AND CHANGE OF OCCUPANCY OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
  
 2) PLEASE NOTE THERE ARE TO DISTINCT WORK AREAS IN THIS
 BUILDING, A CHANGE IN OCCUPANCY AND ALTERATIONS OR
 REMODELING. PLEASE ALSO NOTE THAT WORK AREAS NOT
 PREVIOUSLY AIR CONDITIONED ARE CONSIDERED ADDITIONS
 UNDER THE ENERGY CODE. SEE THE 2017 FBC-ENERGY CODE
 DEFINITIONS: ADDITION. AN EXTENSION OR INCREASE IN THE
 CONDITIONED SPACE FLOOR AREA OR HEIGHT OF A BUILDING OR
 STRUCTURE.
  
 3) SHEET 003_D101 NOTE W07 INDICATES THE REMOVAL OF A
 MASONRY WALL AND ON THE INTERIOR SIDE OF THE OFFICE THE
 DRYWALL TO CREATE A NEW OPENING. SHEET 016_S1.1 DOES
 HAVE A NOTE FOR THE NEW OPENING THAT ON THE ONE SIDE OF
 THE NEW OPENING THERE APPEARS TO BE A FILLED CELL AND
 THE OTHER SIDE OF THE NEW OPENING A NEW GROUTED SOLID
 CELL WITH (1)- #5 VERTICAL. THE NEW OPENING IS TO BE
 FROM FINISH FLOOR 0?-0? TO 12 FEET ABOVE FINISH FLOOR.
 WHAT THE PLANS ARE NOT CLEAR ON IS AT THE 12 FOOT
 ELEVATION IS THERE A EXISTING BEAM OR IS A NEW LINTEL
 REQUIRED. THE OTHER ISSUE IS THE PLANS DO NOT INDICATE
 IF THE NEW VERTICAL REBAR IS REQUIRED TO BE DOWELLED
 INTO THE FLOOR SLAB, AND BEAM ABOVE OR INTO THE LINTEL.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 4A) SHEET 005_A101 THE FLOOR PLAN DOES INDICATE WITH
 NOTE 0850 NEW STOREFRONT TO BE INSTALLED IN EXISTING
 OVERHEAD DOOR OPENING, THIS HAPPENS IN 2 AREAS, ALSO
 NOTE 1550 STATES A NEW WINDOW IS TO BE INSTALLED. SHEET
 009_A105 DOES NOTE THAT THESE OPENINGS ARE TO BE
 DEFERRED SUBMITTALS. PLEASE SHOW COMPLIANCE WITH:
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 4B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 4C) THE SHEET 005_A101 SHOWS THE NEW WINDOW
 INSTALLATION WITH NOTE 1550 BUT WHEN YOU GO TO THE
 ELEVATION SHEET THIS SAME WINDOW IS IDENTIFIED WITH
 MARKER NUMBER 0852 WHICH STATES EXISTING STOREFRONT
 EGRESS DOOR TO REMAIN. DISCREPANCY IN PLANS, PLEASE
 CORRECT. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET 009_A105 STOREFRONT ASSEMBLIES DOES PROVIDE
 THE WIND DESIGN CRITERIA AND ASSOCIATED PRESSURES FOR
 THE NEW WINDOW INSTALLATIONS. THE WIND CHART INDICATES
 THE VULT WIND SPEED AT 143 MPH. THE CODE DOES ALLOW YOU
 TO INTERPOLATE BETWEEN WIND SPEED LINES. PLEASE REVIEW
 THE W.P.B. AMENDMENTS AND PALM BEACH COUNTY ULTIMATE
 DESIGN WIND SPEED MAP WITH WIND SPEED LINES FOR WIND
 FOR RISK CATEGORY II BUILDINGS THERE ARE NO 140 VULT
 WIND SPEED LINES IN PALM BEACH COUNTY, NOT UNTIL YOU
 GET OVER INTO GLADES AND HIGHLANDS DO YOU GET TO VULT
 WIND SPEED LINES BETWEEN 140 AND 150 FOR BUILDINGS WITH
 A RISK CATEGORY II. ALSO SEE THE 2017 FBC-B FIGURE
 1609.3(1) WIND SPEED FOR RISK CATEGORY II BUILDINGS AND
 STRUCTURES. PALM BEACH COUNTY UNINCORPORATED AREAS AND
 ALL MUNICIPALITIES ADOPTED LOCALLY PALM BEACH COUNTY
 WIND SPEED MAPS. WHEN YOU INTERPOLATE BETWEEN THE WIND
 SPEED LINES FOR A BUILDING WITH II RISK CATEGORY THE
 VULT WIND SPEED WOULD BE 168.75 MPH.
  
 6) THE SECOND ISSUE WITH THE WIND DESIGN CRITERIA IS
 CLASSIFYING THE EXPOSURE AS A B EXPOSURE. WHEN VIEWING
 THIS LOCATION USING PALM BEACH COUNTY GEO NAV IT
 CLEARLY SHOWS TO THE NORTHEAST, EAST, SOUTHEAST IS THE
 BALL PARK OPEN GRASS LANDS. THE OTHER AREAS WHERE YOU
 HAVE A C EXPOSURE IS ALSO TO THE NORTHWEST. PLEASE
 CORRECT THE WIND SPEED AND EXPOSURE, WITH THE HEIGHT
 AND EXPOSURE ADJUSTMENT COEFFICIENT TAKEN FROM ASCE
 7-10 THE PRESSURES WILL DEFINITELY BE GREATER FOR THE
 WALL ZONE 4. PLEASE ALSO PROVIDE THE WALL ZONE
 PRESSURES IN VASD SINCE ALL OF THE PRODUCT APPROVALS
 ARE TESTED IN VASD.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 6.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 6.2. RISK CATEGORY.
  
 6.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 6.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 6.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF
 LINE.
  
 7) SHEET 010_A201 ROOF PLAN PLEASE SEE NOTE 0750
 INDICATES THERE IS AN EXISTING ROOF HATCH, NOT SHOWN ON
 THE PLANS. PLEASE PROVIDE THE LOCATION OF THE EXISTING
 ROOF HATCH OR COMPLIANCE WITH:
 2017 FBC-B 1011.16 LADDERS. PERMANENT LADDERS SHALL NOT
 SERVE AS A PART OF THE MEANS OF EGRESS FROM OCCUPIED
 SPACES WITHIN A BUILDING. PERMANENT LADDERS SHALL BE
 PERMITTED TO PROVIDE ACCESS TO THE FOLLOWING AREAS:
 1. SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE,
 REPAIR OR MONITORING OF EQUIPMENT.
 5. NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE
 STAIRWAY ACCESS IN ACCORDANCE WITH SECTION
 1011.12.1.
 6. LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 SECTION 306.5 OF THE FLORIDA BUILDING CODE,
 MECHANICAL.
 LADDERS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS.
  
 8A) SHEET 010_A201 ROOF PLAN PLEASE SEE NOTE 0705
 INDICATES THE INSTALLATION OF NEW TAPERED ROOF
 INSULATION CRICKETS OVER STEEL DECK. MEMBRANE TO MATCH
 EXISTING USING THE MANUFACTURERS STANDARD DETAIL.
 PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE ROOFING
 REPAIRS, THIS CAN BE A DEFERRED SUBMITTAL UPON REQUEST.
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
  
 8B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) SHEET 010_A201 NOTE 1519 INDICATES NEW ROOFTOP
 MECHANICAL EQUIPMENT. NOTE INDICATES SEE CURB DETAIL
 THIS SHEET. NOTES ON DETAIL INDICATE REFER TO MECH.
 DRAWINGS TO SECURE TO THE EXISTING ROOF DECK PER
 MANUFACTURERS RECOMMENDATIONS. THE MECHANICAL SHEET
 025_M701 DETAIL 1 INDICATES IN NOTES 18 INCH INSULATED
 ROOF CURB REFER TO ARCHITECTURAL DETAIL 2/A2.1. THERE
 IS NO SUCH SHEET. THE STRUCTURAL ROOF FRAMING PLAN
 THERE IS NO DETAIL OF HOW TO ANCHOR THE ROOF TOP CURB
 TO THE ROOF FRAMING MEMBERS NOR THE ROOF TOP UNIT TO
 THE CURB. THIS IS ALSO TRUE WHERE THERE ARE NOTES FOR
 ROOF TOP CURB ADAPTORS.
  
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 10) PLEASE NOTE NONE OF THE PLANS PROVIDE THE WIND
 ANALYSIS FOR ROOF ZONES 1, 2, & 3 AND THE ASSOCIATED
 PRESSURES. PLEASE ALSO SUPPLY THE HEIGHT OF THE PARAPET
 IN THE DESIGN CRITERIA. SHEETS 010_A201 AND OR
 017_S2.1.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 ROOFS NO ZONE 3/ PARAPET. ASCE 7-10 FIGURE 30.4-2A.
 FOOTNOTE 5. IF A PARAPET IS EQUAL TO OR HIGHER THAN 3
 FEET IS PROVIDED AROUND THE PERIMETER OF THE ROOF WITH
 0<7 DEGREES THE NEGATIVE VALUE OF GCP IN ZONE 3 SHALL
 BE EQUAL TO THOSE IN ZONE 2 AND THE POSITIVE VALUES OF
 GCP IN ZONES 2 AND 3 SHALL BE EQUAL TO THOSE IN WALL
 ZONES 4 AND 5 RESPECTIVELY, SEE FIGURE 30.4-1.
  
 11) SHEET 015_S0.1 DOES PROVIDE DETAILS FOR WELDING AT
 THE NEW ROOF TOP OPENINGS, AND REQUIRED BRACING OF THE
 BAR JOIST AND ADDITIONAL STEEL FRAMING MEMBERS (WELDED)
 AS WELL AS DECK OPENING REPAIRS, FRAMING AND DECK
 SCREWS. PLEASE SHOW COMPLIANCE WITH WELDED OR BOLTED
 CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2) QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
  
 12) THE PLANS DO NOT SHOW THESE ACCESSIBLE ELEMENTS:
 12A) 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE 2003 IBC-B 1007.1 WHERE
 MORE THAN ONE MEANS OF EGRESS IS REQUIRED BY SECTIONS
 1014.1 OR 1018.1 FROM ANY ACCESSIBLE SPACE, EACH
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO MEANS OF EGRESS.
  
 12B) BREAK ROOM SINK, AND COFFEE ROOM SINK. 606
 LAVATORIES AND SINKS. 2017 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 12C) BREAK ROOM SEATING. ) 902.1 .DINING SURFACES AND
 WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE, BUT
 ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND
 BOOTHS. EXAMPLES OF WORK SURFACES INCLUDE WRITING
 SURFACES, STUDY CARRELS, STUDENT LABORATORY STATIONS,
 BABY CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA
 SCOPING PROVISIONS, EMPLOYEE WORK STATIONS.
  
 12C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 12C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 12D) UNKNOWN IF MICROWAVES ARE TO BE INSTALLED AND
 WHERE, AT WHAT HEIGHT.
 308 REACH RANGES:
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS :
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 12E) EITHER THE DESIGNER OF RECORD OR THE CONTRACTOR ON
 THEIR LETTERHEAD TO PRODUCE A LETTER WHERE UP TO
 $80,000.00 DOLLARS IN A ITEMIZED LIST WHERE THE
 ACCESSIBILITY UPGRADES HAVE BEEN SPENT COMPLYING WITH:
 2017 ACCESSIBILITY CODE SECTION:
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 13) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved