2019-09-10 13:49:30GAS COMMENTS: APPROVED W/PROVISO
  
 1. ONE (1) EACH STAMPED AND SEALED PLAN SHEET ES1.01
 SHALL BE PROVIDED FOR REVIEWERS? NOTATIONS AS
 APPLICABLE INTO SET OF PLANS WHICH WAS MISSING THIS
 PAGE.
 2. FUTURE GENERATOR AND ASSOCIATED GAS PIPING SHOWN ON
 PLAN SHEET ES1.01 IS NOT PART OF THIS PROJECT AND SHALL
 REQUIRE A SEPARATE PERMIT.
 3. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA
 SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR THE FIRE
 PIT INDICATING 50 MBTU. THE DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO THE FIRST GAS
 ROUGH INSPECTION.
 4. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA
 SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR THE
 TANKLESS WATER HEATERS.INDICATING 199 MBTU EACH. THE
 DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON SITE
 PRIOR TO THE FIRST GAS ROUGH INSPECTION.
 5. SEE PLAN SHEET ES1.01 FOR LOCATION OF FPU GAS METER.
 6. RE: PLAN SHEET P1.02; PRIOR TO FINAL INSPECTION, A
 RECORD DRAWING SHALL BE PROVIDED NOTING THE FIRE PIT AS
 50 MBTU.
 7. CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION.
 CALL 561-805-6692 FOR FURTHER INFORMATION.
 8. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL