2019-09-06 07:17:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010578
 ADD: 2717 POINSETTIA AVE.
 CONT: PA TWIN MANAGEMENT/ CGC1525857
 TEL: 561-345-9054
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. SEPT. 06, 2019
  
 ACTION: BUILDING PROVISOS
  
 1) PROVISO: PLEASE NOTE THAT THAT THE BIRTHING CENTER
 SHALL COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR
 BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND
 PROGRAMMATIC PROVISIONS, THE AGENCY OF HEALTH CARE
 ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES.
 FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES
 THAT THE AGENCY (AHCA) MAY ENFORCE THE
 SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING
 CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY
 ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA
 BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO
 ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL-
 OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF
 THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE
 ACCESSIBILITY CODE.
 PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE
 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE
 DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE
 COMPLIANCE.
  
 2) PROVISO: A SEPARATE PERMIT IS REQUIRED FOR FIRE
 SPRINKLERS. IN THE 2017 EXISTING BUILDING CODE FOR
 CHANGE OF OCCUPANCY CHAPTER 10 OF THE EXISTING B. C.
 SECTION 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER
 SYSTEM IN THE PORTION OF THE BUILDING THAT REQUIRES A
 FIRE SPRINKLER SYSTEM, WHEN SEPARATION (HORIZONTAL) IS
 INSTALLED BY OTHER REQUIREMENTS IN THE CODE. SECTION
 1004 E. B. C. FIRE PROTECTION IS REQUIRED IN CHAPTER 9
 OF THE FBC-B. SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA
 13R SPRINKLER SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN
 GROUP R OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN
 HEIGHT IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM)
 IN HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE
 INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R.
  
 AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP
 TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS
 NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE
 PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN
 ACCORDANCE WITH NFPA 13R.
  
 3) PROVISO: SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR
 SHOWS A TABLE AND CHAIRS LISTED AS 120, AND LISTED
 STAFF AREA, WILL ANY OF THE CUSTOMERS AND OR RELATIVE
 EVER BE ABLE TO USE THIS AREA FOR EITHER SNACKS OR
 MEALS? IF SO THEN COMPLIANCE WILL BE REQUIRED WITH THE
 2017 ACCESSIBILITY CODE SECTIONS:
  
 3)(A) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
 EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES,
 STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY
 CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA
 SCOPING PROVISIONS, EMPLOYEE WORK STATIONS.
  
 3)(B) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3)(C) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3(D) NEW COMMENT) SHEET A1.2 SHOWS A MICROWAVE OVER THE
 STOVE, HEIGHT NOT GIVEN BUT MUST COMPLY WITH THE
 ACCESSIBILITY CODE
 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 (22.2 N) MAXIMUM.
  
 4) PROVISO: REVISION REQUIRED. SHEET A7.01 HAS A WINDOW
 AND DOOR SCHEDULE. THE WINDOW SCHEDULE INDICATES SEE
 STRUCTURAL SHEETS FOR WIND DESIGN & PRESSURES. THE DOOR
 SCHEDULE INDICATES SEE ELEVATIONS FOR WIND DESIGN AND
 ASSOCIATED PRESSURES. A REVISION IS REQUIRED SHOWING
 THE REQUIRED WIND DESIGN CRITERIA AND ASSOCIATED
 PRESSURES, PLUS PRODUCT APPROVALS FOR ALL NEW WINDOWS,
 EXTERIOR DOORS AND NEW ROOFING.
  
 4A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 4B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,
 (B) WINDOWS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER