Plan Review Notes
Plan Review Notes For Permit 19010578
Permit Number 19010578
Review Stop P
Sequence Number 2
Notes
Date Text
2019-06-04 10:28:35ADDED COMMENTS EMAILED 6/4/2019 TO AUSTIN DUFFY OF PA
 TWIN MANAGEMENT
 REGARDING THE BIRTHING CENTER AT 2717 POINSIATTIA AVE;
 PERMIT #19010578
 PLEASE NOTE THAT I PERFORMED A COMPREHENSIVE REVIEW OF
 THE PLUMBING ON 5/30/2019. AFTER ADDITIONAL
 CONSIDERATION I WANT TO BRING SOME ADDITIONAL POTENTIAL
 ISSUES TO LIGHT THAT SHOULD BE CONSIDERED BY THE
 DESIGNERS OF RECORD. PLEASE FORWARD TO THOSE DESIGN
 PROFESSIONALS FOR THEIR CONSIDERATION IN PREPARING THE
 NEXT SUBMITTAL.
 ITEM 1: PLEASE NOTE THE FOLLOWING SECTIONS OF THE
 FLORIDA BUILDING CODE.
 ? 452.1SCOPE.
 ALL BIRTHING CENTERS SHALL COMPLY WITH THE FOLLOWING
 DESIGN AND CONSTRUCTION STANDARDS AS DESCRIBED HEREIN.
 NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS
 MAY APPLY. SEE AGENCY OF HEALTH CARE ADMINISTRATION
 [AHCA] RULE 59A-11, FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 383, FLORIDA STATUTES.
  
 ? FBC 452.2.2.3
 A SEPARATE SPACE FOR A CLEAN AREA AND A CONTAMINATED
 AREA; IF IT IS NOT FEASIBLE TO PROVIDE SUCH SEPARATE
 AREAS, SPECIAL PROCEDURES SHALL BE ESTABLISHED FOR THE
 DISPOSAL OF INFECTIOUS WASTE. SANITARY WASTE
 CONTAINERS, SOILED LINEN CONTAINERS, STORAGE CABINETS
 AND AN AUTOCLAVE, PRESSURE COOKER OR OTHER EFFECTIVE
 STERILIZATION EQUIPMENT SHALL BE AVAILABLE.
 ? 452.2.11LAUNDRY.
 452.2.11.1
 WHERE LAUNDRY FACILITIES ARE PROVIDED, LAUNDRY
 FACILITIES SHALL BE OF SOUND CONSTRUCTION AND SHALL BE
 IN GOOD REPAIR AND CLEAN. ADEQUATE SPACE SHALL BE
 PROVIDED AND AREAS SHALL BE DESIGNATED FOR THE
 SEPARATION OF CLEAN AND SOILED CLOTHING, LINEN AND
 TOWELS.
  
 PLEASE REVIEW THE PLANS TO INSURE COMPLIANCE WITH THESE
 SECTIONS. IF SPECIAL PROCEDURES FOR DISPOSAL OF
 INFECTIOUS WASTE ARE TO BE EMPLOYED, THEN PLEASE STATE
 THE SAME ON THE PLANS TO SHOW COMPLIANCE.
 DISCHARGES FROM AUTOCLAVES AND OTHER STERILIZERS TO THE
 SANITARY SYSTEM SHALL COMPLY WITH FBC PL CHAPTER 8 AND
 SECTION 713.
  
 ITEM 2: BIRTHING TUB DRAINAGE
 ? 452.2.3.4
 ALL FLOOR SURFACES, WALL SURFACES, WATER CLOSETS,
 LAVATORIES, TUBS, SHOWERS, SHALL BE KEPT CLEAN, AND ALL
 APPURTENANCES OF THE STRUCTURES SHALL BE OF SOUND
 CONSTRUCTION, PROPERLY MAINTAINED, IN GOOD REPAIR AND
 FREE FROM SAFETY HAZARDS.
 REGARDING THE BIRTHING TUBS, THE ELIMINATION OF THE
 OVERFLOW WAS DONE TO ELIMINATE BACTERIA FORMING IN THAT
 SPACE. HOWEVER, THE TUB WASTE IS A DIRECT CONNECTION TO
 THE SANITARY WHICH CAN ALLOW A STOPPAGE TO BACK UP INTO
 THE TUB POTENTIALLY INTRODUCING HAZARDOUS BACTERIA INTO
 THE VESSEL. THIS CONDITION CAN BE ELIMINATED BY
 DISCHARGING THE TUB DRAIN INTO A TRAPPED AND VENTED
 INDIRECT WASTE RECEPTOR WITH AN AIR GAP. IF THE TRAPPED
 AND VENTED DIRECT CONNECTION TO THE SANITARY CONTINUES
 TO BE THE CHOICE BY THE DESIGN ENGINEER THEN IT MUST BE
 INSTALLED IN A MANNER THAT DOES NOT ALLOW THE FIXTURE
 DRAIN TO CONNECT TO THE VENT BELOW THE TRAP.
  
2019-05-30 13:53:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLEASE NOTE THAT THE LETTER SIGNED AND SEALED, DATED
 5/21/2019, PROVIDED BY STUDIO SR ARCHITECTURE AND
 DESIGN REQUESTING THAT OVERFLOWS NOT BE REQUIRED FOR
 THE BIRTHING TUB(S) HAS BEEN REVIEWED BY THIS
 DEPARTMENT AND THE TUB(S) ARE APPROVED AS NOTED ON THE
 SUBMITTALS.
  
 PLUMBING COMMEMTS: DENIED
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. THE FOLLOWING COMMENTS ARE OFFERED AS A GUIDE
 BUT MAY NOT BE ALL INCLUSIVE. ALL REQUIREMENTS MUST BE
 SATISFACTORILY ADDRESSED ON THE PLANS PRIOR TO A
 PLUMBING REVIEW APPROVAL.
 A. 212.3 SINKS. WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606.
 B. PROVIDE PLAN VIEW DETAILS OF KITCHEN CONFORMING TO
 FBC ACC 804.3.1
 C. PROVIDE ELEVATION DETAILS OF KITCHEN CONFORMING TO
 FBC ACC 804.3.2
 D. ALL OPERABLE PARTS SHALL MEET THE REQUIREMENTS OF
 FBC ACC 309.
 E. SHOW ALL REQUIRED CLEAR FLOOR SPACES AND TURNING
 RADIUS AS REQUIRED BY FBC ACC 305.
 F. PROVIDE DETAILS (PLAN AND ELEVATION) OF ALL
 COMPLIANT FIXTURES SHOWING COMPLIANCE WITH FBC ACC
 CHAPTER 3 AND CHAPTER 6. INCLUDE ALL GRAB BARS, SHOWER
 SEATS, CONTROLS, TOILET ROOM ACCESSORIES AND RELATED
 MILLWORK.
 G. SEE FBC ACC 604.8.1.2. TOILET ROOM DOORS SHALL BE
 LOCATED IN THE FRONT PARTITION OR IN THE SIDE WALL OR
 PARTITION FARTHEST FROM THE WATER CLOSET. WHERE LOCATED
 IN THE FRONT PARTITION, THE DOOR OPENING SHALL BE 4
 INCHES (100 MM) MAXIMUM FROM THE SIDE WALL FARTHEST
 FROM THE WATER CLOSET. WHERE LOCATED IN THE SIDE WALL
 OR PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100
 MM) MAXIMUM FROM THE FRONT PARTITION. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
 H. TOILET ROOM(S) ACCESSIBLE TO THE WAITING AREA SHALL
 MEET THE REQUIREMENTS OF FBC ACC 213
 2. PER FBC PL 403.1, 403.2 AND TABLE 403.1, BASED UPON
 THE OCCUPANT LOAD, SEPARATE TOILET ROOM FACILITIES ARE
 REQUIRED FOR EACH SEX AND MUST BE ACCESSIBLE FROM THE
 WAITING ROOM. THE DESIGN CRITERIA FOR THE PROJECT
 INCLUDED 2017 EXISTING BUILDING CODE CHAPTER 801,
 SECTION 801.3. PLEASE NOTE CHAPTER 810 CONCERNING
 PLUMBING WHICH MAY ALLOW AN EXCEPTION TO THE SEPARATE
 FACILITIES REQUIREMENT.
 3. PER FBC PL 403.1 AND TABLE 403.1, BASED UPON THE
 OCCUPANT LOAD, A DRINKING FOUNTAIN IS REQUIRED; SAID
 DRINKING FOUNTAIN SHALL MEET THE REQUIREMENTS OF 410.1
 AND 410.3 (MINIMUM TWO REQUIRED, ONE FOR WHEELCHAIR AND
 ONE FOR STANDING, OR SINGLE BI-LEVEL), AS WELL AS
 MEETING THE REQUIREMENTS OF FBC ACC 211.2 AND 602.
 4. SINKS FROM LAB RM #126 AND CONSULTATION 2 RM #123
 SHALL NOT CONNECT TO THE WET VENT SERVICING BATH #2 RM
 #113 PER FBC PL 912.1 AND FBC RES P3108.1. CONNECT TO
 BRANCH DOWNSTREAM OF BATHROOM FIXTURES AHEAD OF BRANCH
 SERVICING BATH 1 RM #105 AND BIRTH RM 1 RM #112. MAKE
 CORRECTION ON P1.01 AND P2.01 PER WPB FBC 107.2.1.
 5. RE: P2.01 SANITARY ISOMETRIC; A SINK IS SHOWN
 CONNECTING TO BRANCH BETWEEN BATH #2 AND BIRTH #1
 TUB/BATH #1. THIS SINK DOES NOT APPEAR ON P1.01 OR
 A102.1 FLOOR PLANS. PLEASE CLARIFY PER WPB FBC 107.2.1.
 6. PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING
 INFORMATION:
 A. IDENTIFY GAS TANKLESS WATER HEATERS ON P1.01 FLOOR
 PLAN AND INTEGRATE WITH WATER DISTRIBUTION.
 B. ON P2.01 TANKLESS HOT WATER SYSTEM DETAIL, PROVIDE
 ADDITIONAL DETAIL INTEGRATING THE POTABLE WATER SERVICE
 WITH THE HOT WATER SYSTEM AND TO HOUSE DISTRIBUTION.
 C. PROVIDE SCHEDULE, DETAIL AND SPECIFICATION FOR HOT
 WATER RECIRCULATING PUMP; INCLUDE ELECTRICAL
 CHARACTERISTICS AND CONTROLS. COMPLY WITH THE
 REQUIREMENTS OF FBC EC C404 AND FBC PL 607.
 7. REGARDING THE SIZING OF THE WATER DISTRIBUTION
 SYSTEM, PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR
 SIZING OF THE SYSTEM. IDENTIFY FIXTURE, QUANTITY AND
 WSFU/ GPM FOR EACH FIXTURE WITH TOTALS FOR COLD AND HOT
 WATER.
 8. REGARDING ?PLUMBING SPECIFICATIONS? ON P2.01, PER
 WPB FBC 107.2.1, MAKE THE FOLLOWING CHANGES:
 A. SECTION 2-CODES AND STANDARDS; REPLACE ?STANDARD
 PLUMBING CODE (SBCCI)? WITH ?FLORIDA PLUMBING CODE 2017
 6TH EDITION?
 B. SECTION 5, -MATERIALS, ITEM F ; REPLACE ?AIR CHAMBER
 OR SHOCK ABSORBERS? WITH ?WATER HAMMER ARRESTORS
 CONFORMING TO ASSE 1010?. ADD AT THE END OF NOTE ?AND
 AT DISHWASHER, ICE LINE AND CLOTHES WASHER.?
 C. SECTION 5 -MATERIALS, ADD SPECIFICATION FOR
 INSULATION OF THE HOT WATER CONFORMING TO THE
 REQUIREMENTS OF FBC EC C404.
 9. REGARDING THE WATER DISTRIBUTION SYSTEM, PER WPB FBC
 107.2.1, PROVIDE FULL OPEN VALVE ON EACH DOWN FEED PIPE
 PER FBC PL 606.1(5) AND SHOW ON THE WATER DISTRIBUTION
 ISOMETRIC. VALVES SHALL BE ACCESSIBLE PER FBC PL 606.3.
 VALVES SHALL BE IDENTIFIED AS REQUIRED BY FBC PL 606.4.
 10. REGARDING THE WATER DISTRIBUTION SYSTEM, PER WPB
 FBC 107.2.1, PROVIDE FULL OPEN VALVE AT THE BASE OF
 SUPPLY TO SECOND FLOOR PER FBC PL 606.1(4) EFFECTIVELY
 PREVENTING IMPACT OF THE FIRST FLOOR SYSTEM AND SHOW ON
 THE WATER DISTRIBUTION ISOMETRIC. THE HOT WATER RETURN
 SHOULD BE MODIFIED TO NEGATE ANY IMPACT ON THE FIRST
 FLOOR. VALVES SHALL BE ACCESSIBLE PER FBC PL 606.3.
 VALVES SHALL BE IDENTIFIED AS REQUIRED BY FBC PL 606.4.
 11. PER WPB CCCM SECTION C PARA III AND IV, A LEAD FREE
 BACKFLOW PREVENTER IS REQUIRED. INDICATE ON P1.01, THE
 LOCATION, SIZE AND TYPE. SHOW ON P2.02 WATER
 DISTRIBUTION ISOMETRIC. INDICATE EXISTING OR NEW. TYPE
 SHALL BE AS REQUIRED BY THE CITY OF WEST PALM BEACH
 UTILITIES (561-822-2244) MEETING THE REQUIREMENTS OF
 WPB CCCM AND FBC PL 608. UP TO DATE CERTIFICATION OF
 THE DEVICE WILL BE REQUIRED FOR FINAL INSPECTION.
 12. PER WPB FBC 107.2.1, NOTE ON THE PLUMBING FIXTURE
 SCHEDULE THE REQUIRED TEMPERATURE LIMITING DEVICES TO
 BE EMPLOYED AT THE FIRST FLOOR LAVATORIES; SHOW
 COMPLIANCE WITH FBC PL 416.5 AND CONFORM TO ASSE 1070
 OR CSA B125.3.
 13. PER WPB FBC 107.2.1, NOTE ON THE PLUMBING FIXTURE
 SCHEDULE THE REQUIRED TEMPERATURE LIMITING DEVICES TO
 BE EMPLOYED AT THE BATHTUBS AND SHOWERS; SHOW
 COMPLIANCE WITH FBC PL 424.5.
 14. REMOVE DUPLICATE ARCHITECTURAL PAGES PER WPB FBC
 107.2.1.
 15. PER WPB FBC 107.2.1, ARCHITECT SHALL LOCATE THE
 WATER METER AND BACKFLOW PREVENTER ON A0.02. AN
 APPROVED PLUMBING REVIEW WILL DEPEND UPON THIS
 REQUIREMENT BEING MET.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19010578 2717 POINSETTIA AVE
  