| 2019-05-21 14:52:35 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19010578 |
| | 5/21/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A1.02 & M1.01: THE REVISED PLANS INDICATE A |
| | 2HR. FIRE-RATED CEILING ASSEMBLY BETWEEN THE 1ST AND |
| | 2ND STORY OF THE TWO-STORY SECTION OF THE BUILDING. |
| | LISTED CEILING RADIATION DAMPERS ARE REQUIRED FOR THE |
| | DUCTS AND DIFFUSERS PENETRATING THE ASSEMBLY- SECTION |
| | 607.2 FBC M. |
| | |
| | 2) A1.02 & M1.01: THE 6X6" AND 6" ROUND AC DUCTS |
| | PENETRATING INTO THE VESTIBULE AND INTERIOR EXIT |
| | STAIRWAY ARE PROHIBITED IN ACCORDANCE WITH SECTIONS |
| | 1023.5 AND 1023.6 FBC B. |
| | |
| | 3) A1.02 & M1.01: THE DRYER AND BATH EXHAUST DUCTS |
| | SHALL NOT PENETRATE INTO THE FIRE-RATED INTERIOR EXIST |
| | STAIRWAY WALL PER SECTION 1023.5 FBC B. |
| | |
| | 4) M1.01: BECAUSE THE NEW BIRTHING CENTER IS A CHANGE |
| | OF OCCUPANCY FROM R-3 TO B, THE AIR HANDLER (AH-1) IS |
| | NO LONGER ALLOWED TO BE INSTALLED IN THE ATTIC- SEE |
| | SECTION C403.2.9.6 FBC EC AND RELOCATE THE UNIT. |
| | |
| | 5) M1.01: THE REQUESTED AC COOLING AND HEATING |
| | CALCULATIONS WERE NOT PROVIDED (SEE 1ST REVIEW COMMENT |
| | #2). THE ENGINEER'S NARRATIVE RESPONSE STATES THAT THE |
| | SYSTEMS ARE LIKE FOR LIKE CHANGEOUTS HOWEVER THERE IS A |
| | PARTIAL MANUAL J HEAT LOAD CALCULATION SHOWN ON THE |
| | PLAN. PLEASE NOTE THAT ACCA MANUAL J CALCULATIONS ARE |
| | FOR SIZING SYSTEMS IN RESIDENTIAL OCCUPANCIES UNDER 3 |
| | STORIES. BECAUSE OF THE CHANGE OF OCCUPANCY AND |
| | INCREASED HEAT LOAD FORM LIGHTING, EQUIPMENT, PEOPLE |
| | ETC, IT IS NECESSARY TO PROVIDE SIZING CALCULATIONS |
| | USING MANUAL N FOR THE BIRTHING CENTER, AND MANUAL J |
| | FOR THE 2ND FLOOR APARTMENT- REFER TO SECTIONS C403.2.1 |
| | AND R403.6.1. AS PREVIOUSLY NOTED IN THE 1ST REVIEW |
| | COMMENT, THE 5-TON SYSTEM AH-2 APPEARS TO BE OVERSIZED |
| | FOR THE APPROXIMATE 778 SF. APARTMENT. |
| | |
| | 6) M1.01: 2ND REQUEST FOR A DUCT SMOKE DETECTOR TO BE |
| | INSTALLED IN THE SUPPLY AIR SYSTEM OF AH-2 PER SECTION |
| | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| | IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE |
| | SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF |
| | SUPPLY AIR |
| | |
| | 7) M1.01: THE NEW KITCHEN EXHAUST HOOD SHALL BE FOR |
| | DOMESTIC USE PER SECTION 505.4 FBC M. PLEASE SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND NOTE THAT MAKEUP AIR |
| | MAY BE REQUIRED PER SECTION 505.2 FBC M. |
| | |
| | 8) M1.01: 2ND REQUEST FOR MANUFACTURER'S SPECIFICATIONS |
| | FOR THE CLOTHES DRYER- SECTION 504.1 FBC M. PLEASE NOTE |
| | THAT MAKEUP AIR SHALL BE PROVIDED IF THE APPLIANCE HAS |
| | AN EXHAUST CAPACITY EXCEEDING 200 CFMS- SECTION 504.6 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |