| 2019-05-30 15:11:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 30A |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | |
| | 2ND REVIEW |
| | GAS COMMENTS: DENIED |
| | 1. EMERGENCY GENERATOR IS INDICATED FUTURE. PLEASE |
| | CLARIFY AS THIS PRESENTS LOGISTICAL COMPLICATIONS FOR A |
| | COMPLETED PROJECT AS WELL AS THE PERMITTING PROCESS. |
| | 2. SUBMIT ON THE ISOMETRIC DRAWING THAT WHICH CLEARLY |
| | SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC FG |
| | SECS. 402.4.1, 402.4.2. |
| | 3. PER WPB FBC 107.2.1, PROVIDE A SCHEDULE INDICATING |
| | GAS TYPE AND CALCULATIONS EACH FOR THE 2 LB. SYSTEM AND |
| | THE .5 LB. SYSTEM. LIST APPLIANCES WITH BTU LOAD WITH |
| | BTU TOTAL AND PROVIDE DISTANCE FROM POINT OF DELIVERY |
| | TO THE MOST REMOTE OUTLET IN THE SYSTEM AND SIZE |
| | ACCORDINGLY USING THE APPROPRIATE TABLES. ALTHOUGH THE |
| | SIZING SHOWN WAS PROBABLY DONE CORRECTLY IT NEEDS TO BE |
| | CLEARLY NOTED ON THE PLANS. IT WOULD BE HELPFUL TO |
| | INCLUDE COPIES OF THE TABLES REFERENCED TO HELP THE |
| | REVIEW PROCESS. |
| | 4. WILL THE DOWNSTREAM MANIFOLD AT THE GAS METER AND |
| | THE PIPING BETWEEN APPLIANCE VALVES AND APPLIANCE |
| | REGULATORS BE GALVANIZED? IF SO, PLEASE INCLUDE IN 2 |
| | LB. CALCULATIONS REFERENCING THE PROPER TABLE AND |
| | INDICATE ON THE PLANS. BE SURE TO USE THE FURTHEST |
| | POINT MEASUREMENT WHEN CALCULATING. INDICATE ALL |
| | GALVANIZED PIPING ON THE GAS RISER. |
| | 5. THE GAS RISER SHOWS 1? TO THE WATER HEATERS, |
| | BRANCHING TO ?? TO EACH OF THE TWO APPLIANCES AS NOTED |
| | IN THE RESPONSE LETTER. HOWEVER THE TANKLESS HOT WATER |
| | SYSTEM DETAIL SHOWS ?? TO THE BRANCHES. PER WPB FBC |
| | 107.2.1, PLEASE RECONCILE DETAIL WITH THE GAS RISER. |
| | 6. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR ALL GAS APPLIANCES AND EQUIPMENT PER WPB FPC |
| | 107.2.1. |
| | 7. PER WPB FBC 107.2.1, INDICATE ON P1.01 THE DISTANCE |
| | FROM THE INTERSECTION OF THE BRANCH TO THE FIRE PIT TO |
| | FPU METER. ARCHITECT SHALL LOCATE THE FPU METER ON |
| | A0.02. AN APPROVED PLUMBING REVIEW WILL DEPEND UPON |
| | THIS REQUIREMENT BEING MET. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19010578 2717 POINSETTIA AVE |
| | |