Date Text
2019-05-30 15:11:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
  
 2ND REVIEW
 GAS COMMENTS: DENIED
 1. EMERGENCY GENERATOR IS INDICATED FUTURE. PLEASE
 CLARIFY AS THIS PRESENTS LOGISTICAL COMPLICATIONS FOR A
 COMPLETED PROJECT AS WELL AS THE PERMITTING PROCESS.
 2. SUBMIT ON THE ISOMETRIC DRAWING THAT WHICH CLEARLY
 SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC FG
 SECS. 402.4.1, 402.4.2.
 3. PER WPB FBC 107.2.1, PROVIDE A SCHEDULE INDICATING
 GAS TYPE AND CALCULATIONS EACH FOR THE 2 LB. SYSTEM AND
 THE .5 LB. SYSTEM. LIST APPLIANCES WITH BTU LOAD WITH
 BTU TOTAL AND PROVIDE DISTANCE FROM POINT OF DELIVERY
 TO THE MOST REMOTE OUTLET IN THE SYSTEM AND SIZE
 ACCORDINGLY USING THE APPROPRIATE TABLES. ALTHOUGH THE
 SIZING SHOWN WAS PROBABLY DONE CORRECTLY IT NEEDS TO BE
 CLEARLY NOTED ON THE PLANS. IT WOULD BE HELPFUL TO
 INCLUDE COPIES OF THE TABLES REFERENCED TO HELP THE
 REVIEW PROCESS.
 4. WILL THE DOWNSTREAM MANIFOLD AT THE GAS METER AND
 THE PIPING BETWEEN APPLIANCE VALVES AND APPLIANCE
 REGULATORS BE GALVANIZED? IF SO, PLEASE INCLUDE IN 2
 LB. CALCULATIONS REFERENCING THE PROPER TABLE AND
 INDICATE ON THE PLANS. BE SURE TO USE THE FURTHEST
 POINT MEASUREMENT WHEN CALCULATING. INDICATE ALL
 GALVANIZED PIPING ON THE GAS RISER.
 5. THE GAS RISER SHOWS 1? TO THE WATER HEATERS,
 BRANCHING TO ?? TO EACH OF THE TWO APPLIANCES AS NOTED
 IN THE RESPONSE LETTER. HOWEVER THE TANKLESS HOT WATER
 SYSTEM DETAIL SHOWS ?? TO THE BRANCHES. PER WPB FBC
 107.2.1, PLEASE RECONCILE DETAIL WITH THE GAS RISER.
 6. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR ALL GAS APPLIANCES AND EQUIPMENT PER WPB FPC
 107.2.1.
 7. PER WPB FBC 107.2.1, INDICATE ON P1.01 THE DISTANCE
 FROM THE INTERSECTION OF THE BRANCH TO THE FIRE PIT TO
 FPU METER. ARCHITECT SHALL LOCATE THE FPU METER ON
 A0.02. AN APPROVED PLUMBING REVIEW WILL DEPEND UPON
 THIS REQUIREMENT BEING MET.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19010578 2717 POINSETTIA AVE
  