| Date |
Text |
| 2019-05-28 09:48:54 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19010578 |
| | ADD: 2717 POINSETTIA AVE. |
| | CONT: PA TWIN MANAGEMENT/ CGC1525857 |
| | TEL: 561-345-9054 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. MAY 28, 2019 |
| | |
| | ACTION: FAILED |
| | |
| | 1) THE ONE SET OF PLANS HAS 2 SETS OF ARCHITECTURAL |
| | SHEETS IN THE SET OF PLANS (REMOVE ONE SET), AND |
| | MISSING SHEETS S1-S5. TE FULL SET OF PLANS THE S-SHEETS |
| | ARE NOT SIGNED AND SEALED. |
| | |
| | 2) THE MECHANICAL SHEETS DOES NOT SHOW RADIENT FIRE |
| | DAMPERS IN THE 2 HOUR FIRE RATED CEILING OF THE FIRST |
| | FLOOR UNDER THE R2 RESIDENCY ABOVE. |
| | 2017 FBC-B 717.6.2 MEMBRANE PENETRATIONS. DUCTS AND AIR |
| | TRANSFER OPENINGS CONSTRUCTED OF APPROVED MATERIALS IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL |
| | THAT PENETRATE THE CEILING MEMBRANE OF A |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| | ASSEMBLY SHALL BE PROTECTED WITH ONE OF THE FOLLOWING: |
| | 1.A SHAFT ENCLOSURE IN ACCORDANCE WITH SECTION 713. |
| | |
| | 2.A LISTED CEILING RADIATION DAMPER INSTALLED AT THE |
| | CEILING LINE WHERE A DUCT PENETRATES THE CEILING OF A |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| | ASSEMBLY. |
| | |
| | 3) MISSING THE WALL DAMPER TO PROTECT THE DUCTWORK |
| | WHERE THE 2ND STORY WALL IS LOCATED. 717.5.6 EXTERIOR |
| | WALLS. (OLD EXTERIOR WALL) DUCTS AND AIR TRANSFER |
| | OPENINGS IN FIRE-RESISTANCE-RATED EXTERIOR WALLS |
| | REQUIRED TO HAVE PROTECTED OPENINGS IN ACCORDANCE WITH |
| | SECTION 705.10 SHALL BE PROTECTED WITH LISTED FIRE |
| | DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING. |
| | |
| | |
| | |
| | BUILDING PROVISOS |
| | |
| | 1) PROVISO: PLEASE NOTE THAT THAT THE BIRTHING CENTER |
| | SHALL COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR |
| | BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND |
| | PROGRAMMATIC PROVISIONS, THE AGENCY OF HEALTH CARE |
| | ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES. |
| | FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES |
| | THAT THE AGENCY (AHCA) MAY ENFORCE THE |
| | SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING |
| | CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY |
| | ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA |
| | BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO |
| | ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL- |
| | OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF |
| | THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE |
| | ACCESSIBILITY CODE. |
| | PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE |
| | 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE |
| | DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE |
| | COMPLIANCE. |
| | |
| | 2) PROVISO: A SEPARATE PERMIT IS REQUIRED FOR FIRE |
| | SPRINKLERS. IN THE 2017 EXISTING BUILDING CODE FOR |
| | CHANGE OF OCCUPANCY CHAPTER 10 OF THE EXISTING B. C. |
| | SECTION 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER |
| | SYSTEM IN THE PORTION OF THE BUILDING THAT REQUIRES A |
| | FIRE SPRINKLER SYSTEM, WHEN SEPARATION (HORIZONTAL) IS |
| | INSTALLED BY OTHER REQUIREMENTS IN THE CODE. SECTION |
| | 1004 E. B. C. FIRE PROTECTION IS REQUIRED IN CHAPTER 9 |
| | OF THE FBC-B. SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA |
| | 13R SPRINKLER SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN |
| | GROUP R OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN |
| | HEIGHT IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM) |
| | IN HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE |
| | INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R. |
| | |
| | AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP |
| | TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS |
| | NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE |
| | PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN |
| | ACCORDANCE WITH NFPA 13R. |
| | |
| | 3) PROVISO: SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR |
| | SHOWS A TABLE AND CHAIRS LISTED AS 120, AND LISTED |
| | STAFF AREA, WILL ANY OF THE CUSTOMERS AND OR RELATIVE |
| | EVER BE ABLE TO USE THIS AREA FOR EITHER SNACKS OR |
| | MEALS? IF SO THEN COMPLIANCE WILL BE REQUIRED WITH THE |
| | 2017 ACCESSIBILITY CODE SECTIONS: |
| | |
| | 3)(A) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES, |
| | STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY |
| | CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL |
| | GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA |
| | SCOPING PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 3)(B) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 3)(C) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3(D) NEW COMMENT) SHEET A1.2 SHOWS A MICROWAVE OVER THE |
| | STOVE, HEIGHT NOT GIVEN BUT MUST COMPLY WITH THE |
| | ACCESSIBILITY CODE |
| | 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE |
| | REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH |
| | REACH. |
| | |
| | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | (22.2 N) MAXIMUM. |
| | |
| | 4) PROVISO: REVISION REQUIRED. SHEET A7.01 HAS A WINDOW |
| | AND DOOR SCHEDULE. THE WINDOW SCHEDULE INDICATES SEE |
| | STRUCTURAL SHEETS FOR WIND DESIGN & PRESSURES. THE DOOR |
| | SCHEDULE INDICATES SEE ELEVATIONS FOR WIND DESIGN AND |
| | ASSOCIATED PRESSURES. A REVISION IS REQUIRED SHOWING |
| | THE REQUIRED WIND DESIGN CRITERIA AND ASSOCIATED |
| | PRESSURES, PLUS PRODUCT APPROVALS FOR ALL NEW WINDOWS, |
| | EXTERIOR DOORS AND NEW ROOFING. |
| | 4A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | 4B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS , |
| | (B) WINDOWS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 4C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |