| | 1ST REVIEW; DENIED |
| | PLUMBING COMMENTS |
| | |
| | 1. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | HAVE NOT BEEN DETERMINED. PLEASE, PROVIDE SO THAT THE |
| | MINIMUM PLUMBING FACILITIES REQUIREMENTS CAN BE |
| | DETERMINED AND PLANS CAN BE REVIEWED FOR COMPLIANCE PER |
| | WPB FBC 107.3.5.1.3 (1). |
| | 2. SINKS FROM LAB RM #126 AND CONSULTATION 2 RM #123 |
| | SHALL NOT CONNECT TO THE WET VENT SERVICING BATH 1 RM |
| | #105 AND BIRTH RM 1 RM #112 PER FBC PL 912.1 AND FBC |
| | RES P3108.1. CONNECT DOWNSTREAM OF TUB. MAKE CORRECTION |
| | ON P1.01 AND P2.01 PER WPB FBC 107.2.1. |
| | 3. P1.01 SECOND FLOOR PLAN INDICATES TWO (2) |
| | LAVATORIES, ONE (1) WATER CLOSET, ONE (1) SHOWER AND |
| | ONE (1) TUB. P2.01 SECOND FLOOR SANITARY ISO INDICATES |
| | TWO (2) LAVATORIES, TWO (2) WATER CLOSETS AND ONE (1) |
| | SHOWER. PLEASE CLARIFY PER WPB FBC 107.2.1. |
| | 4. PROVIDE WATER DISTRIBUTION ISO INDICATING SIZING, |
| | VALVING, REQUIRED BACKFLOW PREVENTERS AND OTHER |
| | APPURTENANCES REQUIRED IN THE SYSTEM PER WPB FBC |
| | 107.3.5.1.3 (3).PROVIDE WATER DISTRIBUTION LAYOUT ON |
| | PLUMBING FLOOR PLAN CORRESPONDING TO THE ISO PER WPB |
| | FBC 107.2.1. |
| | 5. PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING THE |
| | FIXTURE TYPE, WATER REQUIREMENTS, WASTE, REQUIRED |
| | TEMPERATURE LIMITING DEVICES TO BE EMPLOYED WHERE |
| | APPLICABLE AND TYPE OF BACKFLOW PREVENTION REQUIRED |
| | WHERE APPLICABLE PER FWPNB FBC 107.2.1.. |
| | 6. PROVIDE A DETAIL OF THE BIRTHING ROOM TUBS SHOWING |
| | HOW WATER SOURCE IS TO BE APPLIED PER WPB FBC 107.2.1. |
| | |
| | |
| | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS, |
| | ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW |
| | COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |