2019-02-12 15:16:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1. SHOW THE LOCATION FOR THE EMERGENCY GENERATOR AND
 FPU METER PER WPB FBC 107.2.1.
 2. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 APPLIANCES AND EQUIPMENT PER WPB FPC 107.2.1.
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 KITCHEN RANGE PER FBC FG304.1.
 4. SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR PER
 FBC FG 410.1.
 5. PROVIDE TRANSITION COMPATIBLE WITH GAS TYPE AS
 REQUIRED BY FBC FG 403.11 (3) FROM PE PIPING IN THE
 GROUND TO GALVANIZED PIPING ABOVE GROUND ON THE
 HIGH-PRESSURE SIDE OF THE REGULATOR TO COMPLY WITH FBC
 FG 404.17.1 OR PROVIDE MANUFACTURER?S SPECIFICATION AND
 INSTALLATION INSTRUCTIONS FOR FUEL GAS SERVICE HEAD
 ADAPTER RISER TO REGULATOR TO COMPLY WITH FBC FG
 404.17.1 EXCEPTION 1.
 6. NOTE MATERIAL TYPE (SCHEDULE 40 GALVANIZED OR FUEL
 GAS SERVICE HEAD RISER ADAPTER), SIZE AND APPLICABLE
 SIZING TABLE FOR ABOVE GROUND PIPING ON LOW PRESSURE
 SIDE OF THE REGULATOR.
 7. INDICATE SIZE OF LOW PRESSURE PIPING TO EMERGENCY
 GENERATOR PER WPB FBC 107.2.1.
 8. DETAIL ON P2.01 FOR TANKLESS WATER HEATERS INDICATES
 3/4" LOW PRESSURE PIPING TO THE TWO HEATERS AS OPPOSED
 TO 1" ON THE GAS RISER. PLEASE CLARIFY AND CORRECT PER
 WPB FBC 107.2.1.
 9. PLEASE NOTE ON THE PLANS THE TYPE OF GAS PROVIDED
 PER WPB FBC 107.2.1.
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715