| 2019-02-12 15:16:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1. SHOW THE LOCATION FOR THE EMERGENCY GENERATOR AND |
| | FPU METER PER WPB FBC 107.2.1. |
| | 2. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS |
| | APPLIANCES AND EQUIPMENT PER WPB FPC 107.2.1. |
| | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | KITCHEN RANGE PER FBC FG304.1. |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. |
| | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON |
| | THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING |
| | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR |
| | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR PER |
| | FBC FG 410.1. |
| | 5. PROVIDE TRANSITION COMPATIBLE WITH GAS TYPE AS |
| | REQUIRED BY FBC FG 403.11 (3) FROM PE PIPING IN THE |
| | GROUND TO GALVANIZED PIPING ABOVE GROUND ON THE |
| | HIGH-PRESSURE SIDE OF THE REGULATOR TO COMPLY WITH FBC |
| | FG 404.17.1 OR PROVIDE MANUFACTURER?S SPECIFICATION AND |
| | INSTALLATION INSTRUCTIONS FOR FUEL GAS SERVICE HEAD |
| | ADAPTER RISER TO REGULATOR TO COMPLY WITH FBC FG |
| | 404.17.1 EXCEPTION 1. |
| | 6. NOTE MATERIAL TYPE (SCHEDULE 40 GALVANIZED OR FUEL |
| | GAS SERVICE HEAD RISER ADAPTER), SIZE AND APPLICABLE |
| | SIZING TABLE FOR ABOVE GROUND PIPING ON LOW PRESSURE |
| | SIDE OF THE REGULATOR. |
| | 7. INDICATE SIZE OF LOW PRESSURE PIPING TO EMERGENCY |
| | GENERATOR PER WPB FBC 107.2.1. |
| | 8. DETAIL ON P2.01 FOR TANKLESS WATER HEATERS INDICATES |
| | 3/4" LOW PRESSURE PIPING TO THE TWO HEATERS AS OPPOSED |
| | TO 1" ON THE GAS RISER. PLEASE CLARIFY AND CORRECT PER |
| | WPB FBC 107.2.1. |
| | 9. PLEASE NOTE ON THE PLANS THE TYPE OF GAS PROVIDED |
| | PER WPB FBC 107.2.1. |
| | |
| | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS, |
| | ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW |
| | COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |