Plan Review Notes
Plan Review Notes For Permit 19010578
Permit Number 19010578
Review Stop E
Sequence Number 1
Notes
Date Text
2019-02-14 12:43:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. RISER NOTE 3 SHOWS 1/0 CONDUCTORS AS SERVICE
 CONDUCTORS AND FEEDER TO PANEL A. THIS WIRE SIZE IS NOT
 RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(16)
 3. RISER NOTE 7 SHOWS 1/0 CONDUCTORS FROM GENERATOR TO
 TRANSFER SWITCH. THIS WIRE IS NOT RATED TO HANDLE THE
 CALCULATED LOAD, OR THE OUTPUT OF THE GENERATOR.
 PROVIDE CORRECTION. NEC 310.15(B)(16)
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 GENERATORS, SIGNS, AND SITE LIGHTING(WHERE APPLICABLE)
 ARE NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW.
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 6. ELECTRICAL SPECIFICATION 2.C STATES THAT NM CABLE
 SHALL NOT BE USED. HOWEVER, THE PLAN STATES THAT 2ND
 FLOOR CIRCUITS WILL BE RE-USED. PROVIDE CLARIFICATION
 AND/OR CORRECTION. WPB FBC 107.2.1
 7. PROVIDE DETAIL FOR WIRING METHODS IN PATIENT CARE
 AREAS. IDENTIFY ON PLAN WHICH AREAS WILL BE REQUIRED TO
 MEET THESE WIRING METHODS. WPB FBC 107.2.1; NEC 517
 8. LOAD CALCULATION PROVIDED IS THE TYPE USED FOR A
 DWELLING UNIT. THIS WILL NOT BE A DWELLING UNIT.
 PROVIDE ACCURATE LOAD CALCULATION. NEC 220
 9. ALL RECEPTACLE OUTLETS IN LAUNDRY THAT ARE WITHIN 6
 FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
 10. PROVIDE LOCATION OF PANEL B ON PLAN TO CONFIRM CODE
 COMPLIANCE. WPB FBC 107.2.1
 11. BIRTH ROOM 1, RECEPTACLE OUTLETS THAT ARE WITHIN 6
 FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
 12. BIRTH ROOM 1 SHOWS A RECEPTACLE OUTLET LOCATED IN
 THE DOORWAY. PROVIDE CLARIFICATION AND/OR CORRECTION.
 WPB FBC 107.2.1
 13. CONSULTATION ROOM 2, RECEPTACLE OUTLETS THAT ARE
 WITHIN 6 FEET OF THE SINK REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8
 14. EXAM ROOM, RECEPTACLE OUTLETS THAT ARE WITHIN 6
 FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
 15. KITCHEN, RECEPTACLE OUTLETS THAT ARE WITHIN 6 FEET
 OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
 16. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 17. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER