| 2019-02-14 12:43:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 |
| | 2. RISER NOTE 3 SHOWS 1/0 CONDUCTORS AS SERVICE |
| | CONDUCTORS AND FEEDER TO PANEL A. THIS WIRE SIZE IS NOT |
| | RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC |
| | 310.15(B)(16) |
| | 3. RISER NOTE 7 SHOWS 1/0 CONDUCTORS FROM GENERATOR TO |
| | TRANSFER SWITCH. THIS WIRE IS NOT RATED TO HANDLE THE |
| | CALCULATED LOAD, OR THE OUTPUT OF THE GENERATOR. |
| | PROVIDE CORRECTION. NEC 310.15(B)(16) |
| | 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | GENERATORS, SIGNS, AND SITE LIGHTING(WHERE APPLICABLE) |
| | ARE NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS |
| | PRESENT. WPB FBC 105.1, 107.2.1 |
| | 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 6. ELECTRICAL SPECIFICATION 2.C STATES THAT NM CABLE |
| | SHALL NOT BE USED. HOWEVER, THE PLAN STATES THAT 2ND |
| | FLOOR CIRCUITS WILL BE RE-USED. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. WPB FBC 107.2.1 |
| | 7. PROVIDE DETAIL FOR WIRING METHODS IN PATIENT CARE |
| | AREAS. IDENTIFY ON PLAN WHICH AREAS WILL BE REQUIRED TO |
| | MEET THESE WIRING METHODS. WPB FBC 107.2.1; NEC 517 |
| | 8. LOAD CALCULATION PROVIDED IS THE TYPE USED FOR A |
| | DWELLING UNIT. THIS WILL NOT BE A DWELLING UNIT. |
| | PROVIDE ACCURATE LOAD CALCULATION. NEC 220 |
| | 9. ALL RECEPTACLE OUTLETS IN LAUNDRY THAT ARE WITHIN 6 |
| | FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.8 |
| | 10. PROVIDE LOCATION OF PANEL B ON PLAN TO CONFIRM CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 11. BIRTH ROOM 1, RECEPTACLE OUTLETS THAT ARE WITHIN 6 |
| | FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.8 |
| | 12. BIRTH ROOM 1 SHOWS A RECEPTACLE OUTLET LOCATED IN |
| | THE DOORWAY. PROVIDE CLARIFICATION AND/OR CORRECTION. |
| | WPB FBC 107.2.1 |
| | 13. CONSULTATION ROOM 2, RECEPTACLE OUTLETS THAT ARE |
| | WITHIN 6 FEET OF THE SINK REQUIRE GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8 |
| | 14. EXAM ROOM, RECEPTACLE OUTLETS THAT ARE WITHIN 6 |
| | FEET OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.8 |
| | 15. KITCHEN, RECEPTACLE OUTLETS THAT ARE WITHIN 6 FEET |
| | OF THE SINK REQUIRE GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.8 |
| | 16. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| | 17. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |