Plan Review Notes
Plan Review Notes For Permit 19010578
Permit Number 19010578
Review Stop B
Sequence Number 1
Notes
Date Text
2019-02-11 08:30:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010578
 ADD: 2717 POINSETTIA AVE.
 CONT: PA TWIN MANAGEMENT/ CGC1525857
 TEL: 561-345-9054
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 11/2019
 ACTION: DENIED
  
 1) ARCHITECTURAL SHEETS IN THE ARCHITECTS TITLE BLOCK
 IS MISSING: (6) THE PRINTED NAME AND THE
 LICENSE/REGISTRATION NUMBER OF THE PERSON SEALING THE
 DOCUMENT.
 61G1-16.004 TITLE BLOCK. ARCHITECT.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED
  
 2) THE COVERSHEET LIST THE OCCUPANCY TYPE AS AN R3
 OCCUPANCY AND LIST THE CODE SECTION 310.5 OF THE 2017
 FBC-B AND QUOTING THE SECTION ON CARE FACILITIES THAT
 PROVIDE ACCOMMODATIONS FOR FIVE OR FEWER PERSONS
 RECEIVING CARE. WHAT THE DESIGNER HAS OVERLOOKED IS IN
 THE CODE SECTION 310.5 THE RELEVANT WORDING PRIMARILY
 PERMANENT IN NATURE. THE 2015 IBC COMMENTARY ON THE
 SUBJECT OF CARE FACILITIES, THE INTENT IS TO ALLOW
 PERSONS TO BE CARED FOR IN A RESIDENTIAL, OR HOME,
 ENVIRONMENT, OFTEN BY FAMILY MEMBERS, IN A MANNER THAT
 IS TYPICALLY WITHIN A SINGLE FAMILY TYPE HOME, THIS IS
 TO BE CONSIDERED LONG TERM.
  
 IN THE 2017 FBC-B SECTION 308.4.2 INSTITUTIONAL GROUP
 I-2. FIVE OR FEWER PERSONS RECEIVING MEDICAL CARE.
 A FACILITY WITH FIVE OR FEWER PERSONS RECEIVING MEDICAL
 CARE SHALL BE CLASSIFIED AS GROUP R-3 OR SHALL COMPLY
 WITH THE FLORIDA BUILDING CODE, RESIDENTIAL PROVIDED AN
 AUTOMATIC SPRINKLER SYSTEM IS INSTALLED IN ACCORDANCE
 WITH SECTION 903.3.1. THE COMMENTARY AGAIN DECLARES IT
 TO ALLOW PERSONS TO BE CARED FOR IN A RESIDENTIAL, OR
 HOME, ENVIRONMENT, OFTEN BY FAMILY MEMBERS, IN A MANNER
 THAT IS TYPICALLY WITHIN A SINGLE FAMILY TYPE HOME,
 THIS IS TO BE CONSIDERED LONG TERM.
 THE USE OF THE SPACE (FIRST & SECOND FLOOR) IS GOING TO
 BE HOW WE REVIEW WHAT CODE REQUIREMENTS AN OCCUPANCY
 CAN BE DECLARED. I HAVE MET WITH THE BUILDING OFFICIAL
 ROBERT BROWN, ASSISTANT BUILDING OFFICIAL STEVEN
 KENNEDY AND WITH SAMANTHA HILL THE CHIEF PLANS EXAMINER
 ON THIS MATTER. AS DISCUSSED FOR THIS REVIEW WE ARE
 LOOKING AT THE 1ST FLOOR AS A BUSINESS OCCUPANCY
 OFFERING SERVICES SUCH AS A DOCTOR?S OFFICE AND OR
 DENTIST WITH STATE REQUIREMENTS F. S. 383.309 REQUIRING
 US TO ALSO LOOK INTO THE SPECIAL OCCUPANCY PROVISIONS
 FOR BIRTHING CENTERS FOUND IN THE 2017 FBC-B CHAPTER 4
 AND SECTION 452 FOR BIRTHING CENTERS.
 THIS REVIEW WILL ALSO LOOK AT THE BUILDING AS A MIXED
 USE BUILDING. THE 2ND FLOOR AS A R2 OCCUPANCY SINCE THE
 PLANS INDICATE THE KITCHEN ON THE 1ST FLOOR AS PART OF
 THE BUSINESS OCCUPANCY, EVEN THOUGH THE PLANS STATE A
 CARETAKERS QUARTERS AS PRIMARILY PERMANENT IN NATURE.
 THE 1ST FLOOR AS A BUSINESS OCCUPANCY, SPECIAL
 OCCUPANCY, SECTION 452 FOR BIRTHING CENTERS.
 DWELLING UNIT. A SINGLE UNIT PROVIDING COMPLETE,
 INDEPENDENT LIVING FACILITIES FOR ONE OR MORE PERSONS,
 INCLUDING PERMANENT PROVISIONS FOR LIVING, SLEEPING,
 EATING, COOKING AND SANITATION.
 SLEEPING UNIT. A ROOM OR SPACE IN WHICH PEOPLE SLEEP,
 WHICH CAN ALSO INCLUDE PERMANENT PROVISIONS FOR LIVING,
 EATING, AND EITHER SANITATION OR KITCHEN FACILITIES BUT
 NOT BOTH. SUCH ROOMS AND SPACES THAT ARE ALSO PART OF A
 DWELLING UNIT ARE NOT SLEEPING UNITS.
  
 2A) SHEET A1.02. IN A MIXED USE BUILDING THERE NEEDS TO
 BE A HORIZONTAL FIRE BARRIER BETWEEN THE R2 OCCUPANCY
 UPSTAIRS AND THE BUSINESS OCCUPANCY DOWNSTAIRS. SEE
 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
 711.2.4.2 SEPARATING FIRE AREAS. WHERE THE HORIZONTAL
 ASSEMBLY SEPARATES A SINGLE OCCUPANCY INTO DIFFERENT
 FIRE AREAS, THE ASSEMBLY SHALL HAVE A FIRE-RESISTANCE
 RATING OF NOT LESS THAN THAT REQUIRED BY SECTION
 707.3.10.
 711.2.4.2 SEPARATING FIRE AREAS. WHERE THE HORIZONTAL
 ASSEMBLY SEPARATES A SINGLE OCCUPANCY INTO DIFFERENT
 FIRE AREAS, THE ASSEMBLY SHALL HAVE A FIRE-RESISTANCE
 RATING OF NOT LESS THAN THAT REQUIRED BY SECTION
 707.3.10. TABLE 707.3.10 WILL REQUIRE A 2 HOUR FIRE
 BARRIER BETWEEN THE R2 OCCUPANCY ABOVE AND THE PORTION
 OF THE BUSINESS OCCUPANCY DIRECTLY BELOW THE R2
 OCCUPANCY AS WELL AS BENEATH THE STAIR, 1ST FLOOR
 SHOWER CEILING.
  
 2B) SHEET A1.02. THE NEW STAIRWAY ADDITION WILL NEED TO
 BE SEPARATED VERTICALLY AS WELL AS HORIZONTALLY, THE
 VESTIBULE 2 BOTH HORIZONTALLY AS WELL AS VERTICALLY
 TABLE 508.4 WITH A 2 HOUR FIRE BARRIER.
  
 707.3.9 SEPARATED OCCUPANCIES. WHERE THE PROVISIONS OF
 SECTION 508.4 ARE APPLICABLE, THE FIRE BARRIER
 SEPARATING MIXED OCCUPANCIES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN THAT INDICATED
 IN TABLE 508.4 BASED ON THE OCCUPANCIES BEING
 SEPARATED.
  
 2C) SHEET A1.02. VESTIBULE 2 ALSO SHOWS THE STAIR
 WINDERS AT THE BOTTOM OF THE STAIRWELL. PLEASE INDICATE
 BETWEEN STAIR 1 AND 2 IT APPEARS THE WINDER STAIR GOES
 TO A POINT, THERE IS A DASHED LINE THAT COULD BE THE
 HEADER ABOVE, PLEASE CLARIFY FOR CODE COMPLIANCE WITH
 FBC-B 1011.4. THE 12-INCH (305 MM) DIMENSION SHALL BE
 MEASURED FROM THE WIDEST POINT OF THE CLEAR STAIR WIDTH
 AT THE WALKING SURFACE OF THE WINDER. WHERE WINDERS ARE
 ADJACENT WITHIN THE FLIGHT, THE POINT OF THE WIDEST
 CLEAR STAIR WIDTH OF THE ADJACENT WINDERS SHALL BE
 USED.
  
 3) PLEASE NOTE THAT THE DESIGNER OF RECORD CANNOT USE
 NONSEPARATED OCCUPANCIES BETWEEN THE R2 OCCUPANCY AND
 BUSINESS OCCUPANCY ON THE 1ST FLOOR, SECTION
 508.2.4.(2) TAKES YOU TO SECTION 420 SPECIAL
 OCCUPANCIES FOR GROUPS I-1, R-1,R-2, R-3 AND R-4.
 SECTION 420.2 AND 420.3 SEPARATION WALLS AND HORIZONTAL
 SEPARATION BETWEEN DWELLING UNITS/ SLEEPING UNITS AND
 OTHER OCCUPANCIES.
  
 4) PLEASE ALSO REVIEW FLORIDA STATUTE 383.308 (B) FOR
 FOOD SERVICES, IF JUST LIGHT SNACKS OR IF A FOOD
 SERVICE IS PROVIDED, SPECIAL REQUIREMENTS SHALL BE MET
 AS DEFINED IN RULES PROMULGATED PURSUANT TO CHAPTER
 381.0072 FOOD SERVICES PROTECTION.
  
 5) PLEASE NOTE THAT THAT THE BIRTHING CENTER SHALL
 COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR
 BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND
 PROGRAMMATIC PROVISIONS MAY APPLY. SEE AGENCY OF HEALTH
 CARE ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES.
 FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES
 THAT THE AGENCY (AHCA) MAY ENFORCE THE
 SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING
 CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY
 ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA
 BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO
 ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL-
 OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF
 THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE
 ACCESSIBILITY CODE.
 PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE
 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE
 DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE
 COMPLIANCE.
  
 5.1) PLEASE SHOW COMPLIANCE WITH SECTIONS: FBC-B
 452.2.2.1. BIRTH ROOMS SHALL BE LOCATED TO PROVIDE
 UNIMPEDED, RAPID ACCESS TO AN EXIT OF THE BUILDING
 WHICH WILL ACCOMMODATE EMERGENCY TRANSPORTATION
 VEHICLES.
  
 5.2) 452.2.6 HALLWAYS AND DOORS PROVIDING ACCESS AND
 ENTRY INTO THE BIRTH CENTER AND BIRTH ROOM SHALL BE OF
 ADEQUATE WIDTH AND CONFORMATION TO ACCOMMODATE
 MANEUVERING OF AMBULANCE STRETCHERS AND WHEELCHAIRS.
 THE STRETCHER REQUIREMENTS ARE AMBULANCE STRETCHER 24
 INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS
 THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL
 POSITION. PLEASE SHOW THE STRETCHER GOING DOWN THE
 CORRIDOR, THROUGH THE DOORWAY AND INTO THE BIRTHING
 ROOMS FOR BOTH BIRTHING ROOMS.
  
 6) PLEASE ALSO BE AWARE THAT THE KITCHEN BEING LOCATED
 ON THE 1ST FLOOR, THE BUSINESS OCCUPANCY, COMPLIANCE
 WITH SECTION 904.2.2 OF THE 2017 FBC-B FOR COMMERCIAL
 HOOD AND DUCT SYSTEMS AND 904.3 THE INSTALLATION OF AN
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS TO BE INSTALLED IN
 ACCORDANCE WITH THIS SECTION.
  
 7) IN THE 2017 EXISTING BUILDING CODE FOR CHANGE OF
 OCCUPANCY CHAPTER 10 OF THE EXISTING B. C. SECTION
 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER SYSTEM IN THE
 PORTION OF THE BUILDING THAT REQUIRES A FIRE SPRINKLER
 SYSTEM, WHEN SEPARATION (HORIZONTAL) IS INSTALLED BY
 OTHER REQUIREMENTS IN THE CODE. SECTION 1004 E. B. C.
 FIRE PROTECTION IS REQUIRED IN CHAPTER 9 OF THE FBC-B.
 SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA 13R SPRINKLER
 SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN GROUP R
 OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN HEIGHT
 IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE
 INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R.
  
 AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP
 TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS
 NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE
 PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN
 ACCORDANCE WITH NFPA 13R.
 8) IN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY PLAN,
 JUST A FLOOR PLAN A1.02. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE SECTION 503).
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 9) PLEASE PROVIDE AN ITEMIZED LETTER FROM EITHER THE
 DESIGNER OF RECORD OR THE CONTRACTOR ON THEIR
 LETTERHEAD WHERE 20% OF THEIR BUDGET OR $30,000.00
 DOLLARS WILL BE SPENT IN MAKING ACCESSIBLE UPGRADES TO
 THE 1ST FLOOR. PLEASE REVIEW THE FOLLOWING CODE SECTION
 IN WHAT ORDER THESE FUNDS ARE TO BE SPENT.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 9A) PLEASE NOTE CURRENTLY THERE IS NO ACCESSIBLE
 ENTRANCE. GOGGLE STREET VIEW SHOWS STEPS AND LANDING TO
 THE FRONT DOOR.
  
 9B) THE PLANS DO NOT SHOW TRAVEL DISTANCES AND IF A 2ND
 EGRESS IS REQUIRED ON THE 1ST FLOOR AND THE VESTIBULE 2
 IS GOING TO BE USED AS THE 2ND REQUIRED EGRESS PLEASE
 SHOW ACCOMMODATIONS FOR MANEUVERING OF AMBULANCE
 STRETCHERS TO THE EXTERIOR OF THE BUILDING.
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 9C) SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR SHOWS A
 TABLE AND CHAIRS LISTED AS 120, AND LISTED STAFF AREA,
 WILL ANY OF THE CUSTOMERS AND OR RELATIVE EVER BE ABLE
 TO USE THIS AREA FOR EITHER SNACKS OR MEALS? IF SO THEN
 COMPLIANCE WILL BE REQUIRED WITH THE 2017 ACCESSIBILITY
 CODE SECTIONS:
 9C)(1) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
 EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES,
 STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY
 CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA
 SCOPING PROVISIONS, EMPLOYEE WORK STATIONS.
  
 9C)(2) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 9C)(3) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 10) IMPACT FEES- PAPER SUBMITTALS
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2019-02-05 16:54:46NOTES IN ERROR DELETED PV


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved