| Date |
Text |
| 2019-02-11 08:30:12 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19010578 |
| | ADD: 2717 POINSETTIA AVE. |
| | CONT: PA TWIN MANAGEMENT/ CGC1525857 |
| | TEL: 561-345-9054 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB. 11/2019 |
| | ACTION: DENIED |
| | |
| | 1) ARCHITECTURAL SHEETS IN THE ARCHITECTS TITLE BLOCK |
| | IS MISSING: (6) THE PRINTED NAME AND THE |
| | LICENSE/REGISTRATION NUMBER OF THE PERSON SEALING THE |
| | DOCUMENT. |
| | 61G1-16.004 TITLE BLOCK. ARCHITECT. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED |
| | AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN |
| | THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION |
| | NUMBER OF THE PERSON SEALING THE DOCUMENT. |
| | (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE |
| | REVISED |
| | |
| | 2) THE COVERSHEET LIST THE OCCUPANCY TYPE AS AN R3 |
| | OCCUPANCY AND LIST THE CODE SECTION 310.5 OF THE 2017 |
| | FBC-B AND QUOTING THE SECTION ON CARE FACILITIES THAT |
| | PROVIDE ACCOMMODATIONS FOR FIVE OR FEWER PERSONS |
| | RECEIVING CARE. WHAT THE DESIGNER HAS OVERLOOKED IS IN |
| | THE CODE SECTION 310.5 THE RELEVANT WORDING PRIMARILY |
| | PERMANENT IN NATURE. THE 2015 IBC COMMENTARY ON THE |
| | SUBJECT OF CARE FACILITIES, THE INTENT IS TO ALLOW |
| | PERSONS TO BE CARED FOR IN A RESIDENTIAL, OR HOME, |
| | ENVIRONMENT, OFTEN BY FAMILY MEMBERS, IN A MANNER THAT |
| | IS TYPICALLY WITHIN A SINGLE FAMILY TYPE HOME, THIS IS |
| | TO BE CONSIDERED LONG TERM. |
| | |
| | IN THE 2017 FBC-B SECTION 308.4.2 INSTITUTIONAL GROUP |
| | I-2. FIVE OR FEWER PERSONS RECEIVING MEDICAL CARE. |
| | A FACILITY WITH FIVE OR FEWER PERSONS RECEIVING MEDICAL |
| | CARE SHALL BE CLASSIFIED AS GROUP R-3 OR SHALL COMPLY |
| | WITH THE FLORIDA BUILDING CODE, RESIDENTIAL PROVIDED AN |
| | AUTOMATIC SPRINKLER SYSTEM IS INSTALLED IN ACCORDANCE |
| | WITH SECTION 903.3.1. THE COMMENTARY AGAIN DECLARES IT |
| | TO ALLOW PERSONS TO BE CARED FOR IN A RESIDENTIAL, OR |
| | HOME, ENVIRONMENT, OFTEN BY FAMILY MEMBERS, IN A MANNER |
| | THAT IS TYPICALLY WITHIN A SINGLE FAMILY TYPE HOME, |
| | THIS IS TO BE CONSIDERED LONG TERM. |
| | THE USE OF THE SPACE (FIRST & SECOND FLOOR) IS GOING TO |
| | BE HOW WE REVIEW WHAT CODE REQUIREMENTS AN OCCUPANCY |
| | CAN BE DECLARED. I HAVE MET WITH THE BUILDING OFFICIAL |
| | ROBERT BROWN, ASSISTANT BUILDING OFFICIAL STEVEN |
| | KENNEDY AND WITH SAMANTHA HILL THE CHIEF PLANS EXAMINER |
| | ON THIS MATTER. AS DISCUSSED FOR THIS REVIEW WE ARE |
| | LOOKING AT THE 1ST FLOOR AS A BUSINESS OCCUPANCY |
| | OFFERING SERVICES SUCH AS A DOCTOR?S OFFICE AND OR |
| | DENTIST WITH STATE REQUIREMENTS F. S. 383.309 REQUIRING |
| | US TO ALSO LOOK INTO THE SPECIAL OCCUPANCY PROVISIONS |
| | FOR BIRTHING CENTERS FOUND IN THE 2017 FBC-B CHAPTER 4 |
| | AND SECTION 452 FOR BIRTHING CENTERS. |
| | THIS REVIEW WILL ALSO LOOK AT THE BUILDING AS A MIXED |
| | USE BUILDING. THE 2ND FLOOR AS A R2 OCCUPANCY SINCE THE |
| | PLANS INDICATE THE KITCHEN ON THE 1ST FLOOR AS PART OF |
| | THE BUSINESS OCCUPANCY, EVEN THOUGH THE PLANS STATE A |
| | CARETAKERS QUARTERS AS PRIMARILY PERMANENT IN NATURE. |
| | THE 1ST FLOOR AS A BUSINESS OCCUPANCY, SPECIAL |
| | OCCUPANCY, SECTION 452 FOR BIRTHING CENTERS. |
| | DWELLING UNIT. A SINGLE UNIT PROVIDING COMPLETE, |
| | INDEPENDENT LIVING FACILITIES FOR ONE OR MORE PERSONS, |
| | INCLUDING PERMANENT PROVISIONS FOR LIVING, SLEEPING, |
| | EATING, COOKING AND SANITATION. |
| | SLEEPING UNIT. A ROOM OR SPACE IN WHICH PEOPLE SLEEP, |
| | WHICH CAN ALSO INCLUDE PERMANENT PROVISIONS FOR LIVING, |
| | EATING, AND EITHER SANITATION OR KITCHEN FACILITIES BUT |
| | NOT BOTH. SUCH ROOMS AND SPACES THAT ARE ALSO PART OF A |
| | DWELLING UNIT ARE NOT SLEEPING UNITS. |
| | |
| | 2A) SHEET A1.02. IN A MIXED USE BUILDING THERE NEEDS TO |
| | BE A HORIZONTAL FIRE BARRIER BETWEEN THE R2 OCCUPANCY |
| | UPSTAIRS AND THE BUSINESS OCCUPANCY DOWNSTAIRS. SEE |
| | FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES |
| | SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR |
| | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR |
| | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS |
| | HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. |
| | 711.2.4.2 SEPARATING FIRE AREAS. WHERE THE HORIZONTAL |
| | ASSEMBLY SEPARATES A SINGLE OCCUPANCY INTO DIFFERENT |
| | FIRE AREAS, THE ASSEMBLY SHALL HAVE A FIRE-RESISTANCE |
| | RATING OF NOT LESS THAN THAT REQUIRED BY SECTION |
| | 707.3.10. |
| | 711.2.4.2 SEPARATING FIRE AREAS. WHERE THE HORIZONTAL |
| | ASSEMBLY SEPARATES A SINGLE OCCUPANCY INTO DIFFERENT |
| | FIRE AREAS, THE ASSEMBLY SHALL HAVE A FIRE-RESISTANCE |
| | RATING OF NOT LESS THAN THAT REQUIRED BY SECTION |
| | 707.3.10. TABLE 707.3.10 WILL REQUIRE A 2 HOUR FIRE |
| | BARRIER BETWEEN THE R2 OCCUPANCY ABOVE AND THE PORTION |
| | OF THE BUSINESS OCCUPANCY DIRECTLY BELOW THE R2 |
| | OCCUPANCY AS WELL AS BENEATH THE STAIR, 1ST FLOOR |
| | SHOWER CEILING. |
| | |
| | 2B) SHEET A1.02. THE NEW STAIRWAY ADDITION WILL NEED TO |
| | BE SEPARATED VERTICALLY AS WELL AS HORIZONTALLY, THE |
| | VESTIBULE 2 BOTH HORIZONTALLY AS WELL AS VERTICALLY |
| | TABLE 508.4 WITH A 2 HOUR FIRE BARRIER. |
| | |
| | 707.3.9 SEPARATED OCCUPANCIES. WHERE THE PROVISIONS OF |
| | SECTION 508.4 ARE APPLICABLE, THE FIRE BARRIER |
| | SEPARATING MIXED OCCUPANCIES SHALL HAVE A |
| | FIRE-RESISTANCE RATING OF NOT LESS THAN THAT INDICATED |
| | IN TABLE 508.4 BASED ON THE OCCUPANCIES BEING |
| | SEPARATED. |
| | |
| | 2C) SHEET A1.02. VESTIBULE 2 ALSO SHOWS THE STAIR |
| | WINDERS AT THE BOTTOM OF THE STAIRWELL. PLEASE INDICATE |
| | BETWEEN STAIR 1 AND 2 IT APPEARS THE WINDER STAIR GOES |
| | TO A POINT, THERE IS A DASHED LINE THAT COULD BE THE |
| | HEADER ABOVE, PLEASE CLARIFY FOR CODE COMPLIANCE WITH |
| | FBC-B 1011.4. THE 12-INCH (305 MM) DIMENSION SHALL BE |
| | MEASURED FROM THE WIDEST POINT OF THE CLEAR STAIR WIDTH |
| | AT THE WALKING SURFACE OF THE WINDER. WHERE WINDERS ARE |
| | ADJACENT WITHIN THE FLIGHT, THE POINT OF THE WIDEST |
| | CLEAR STAIR WIDTH OF THE ADJACENT WINDERS SHALL BE |
| | USED. |
| | |
| | 3) PLEASE NOTE THAT THE DESIGNER OF RECORD CANNOT USE |
| | NONSEPARATED OCCUPANCIES BETWEEN THE R2 OCCUPANCY AND |
| | BUSINESS OCCUPANCY ON THE 1ST FLOOR, SECTION |
| | 508.2.4.(2) TAKES YOU TO SECTION 420 SPECIAL |
| | OCCUPANCIES FOR GROUPS I-1, R-1,R-2, R-3 AND R-4. |
| | SECTION 420.2 AND 420.3 SEPARATION WALLS AND HORIZONTAL |
| | SEPARATION BETWEEN DWELLING UNITS/ SLEEPING UNITS AND |
| | OTHER OCCUPANCIES. |
| | |
| | 4) PLEASE ALSO REVIEW FLORIDA STATUTE 383.308 (B) FOR |
| | FOOD SERVICES, IF JUST LIGHT SNACKS OR IF A FOOD |
| | SERVICE IS PROVIDED, SPECIAL REQUIREMENTS SHALL BE MET |
| | AS DEFINED IN RULES PROMULGATED PURSUANT TO CHAPTER |
| | 381.0072 FOOD SERVICES PROTECTION. |
| | |
| | 5) PLEASE NOTE THAT THAT THE BIRTHING CENTER SHALL |
| | COMPLY WITH THE SECTION 452 OF THE 2017 FBC-B FOR |
| | BIRTHING CENTERS AND OTHER ADMINISTRATIVE AND |
| | PROGRAMMATIC PROVISIONS MAY APPLY. SEE AGENCY OF HEALTH |
| | CARE ADMINISTRATION [AHCA] RULE 59A-11, FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 383, FLORIDA STATUTES. |
| | FLORIDA STATUTE 383.308 FOR BIRTHING CENTERS STATES |
| | THAT THE AGENCY (AHCA) MAY ENFORCE THE |
| | SPECIAL-OCCUPANCY PROVISIONS OF THE FLORIDA BUILDING |
| | CODE AND THE FIRE PREVENTION CODE. WHERE THE AGENCY MAY |
| | ENFORCE THE SPECIAL OCCUPANCY PROVISIONS OF THE FLORIDA |
| | BUILDING CODE, THE BUILDING DEPARTMENT IS REQUIRED TO |
| | ENFORCE THE REQUIREMENTS FOUND IN THE SPECIAL- |
| | OCCUPANCY FOR BIRTHING CENTERS FOUND IN SECTION 452 OF |
| | THE 2017 FBC-B AS WELL AS THE 1ST FLOOR THE |
| | ACCESSIBILITY CODE. |
| | PLEASE NOTE SECTION 452 FOR BIRTHING CENTERS OF THE |
| | 2017 FBC-B HAS 16 DIFFERENT SUB-SECTIONS THAT THE |
| | DESIGNER OF RECORD WILL NEED TO FOLLOW FOR CODE |
| | COMPLIANCE. |
| | |
| | 5.1) PLEASE SHOW COMPLIANCE WITH SECTIONS: FBC-B |
| | 452.2.2.1. BIRTH ROOMS SHALL BE LOCATED TO PROVIDE |
| | UNIMPEDED, RAPID ACCESS TO AN EXIT OF THE BUILDING |
| | WHICH WILL ACCOMMODATE EMERGENCY TRANSPORTATION |
| | VEHICLES. |
| | |
| | 5.2) 452.2.6 HALLWAYS AND DOORS PROVIDING ACCESS AND |
| | ENTRY INTO THE BIRTH CENTER AND BIRTH ROOM SHALL BE OF |
| | ADEQUATE WIDTH AND CONFORMATION TO ACCOMMODATE |
| | MANEUVERING OF AMBULANCE STRETCHERS AND WHEELCHAIRS. |
| | THE STRETCHER REQUIREMENTS ARE AMBULANCE STRETCHER 24 |
| | INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS |
| | THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL |
| | POSITION. PLEASE SHOW THE STRETCHER GOING DOWN THE |
| | CORRIDOR, THROUGH THE DOORWAY AND INTO THE BIRTHING |
| | ROOMS FOR BOTH BIRTHING ROOMS. |
| | |
| | 6) PLEASE ALSO BE AWARE THAT THE KITCHEN BEING LOCATED |
| | ON THE 1ST FLOOR, THE BUSINESS OCCUPANCY, COMPLIANCE |
| | WITH SECTION 904.2.2 OF THE 2017 FBC-B FOR COMMERCIAL |
| | HOOD AND DUCT SYSTEMS AND 904.3 THE INSTALLATION OF AN |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS TO BE INSTALLED IN |
| | ACCORDANCE WITH THIS SECTION. |
| | |
| | 7) IN THE 2017 EXISTING BUILDING CODE FOR CHANGE OF |
| | OCCUPANCY CHAPTER 10 OF THE EXISTING B. C. SECTION |
| | 1012.1.1.2 ONLY REQUIRES A FIRE SPRINKLER SYSTEM IN THE |
| | PORTION OF THE BUILDING THAT REQUIRES A FIRE SPRINKLER |
| | SYSTEM, WHEN SEPARATION (HORIZONTAL) IS INSTALLED BY |
| | OTHER REQUIREMENTS IN THE CODE. SECTION 1004 E. B. C. |
| | FIRE PROTECTION IS REQUIRED IN CHAPTER 9 OF THE FBC-B. |
| | SEE THE 2017 FBC-B SECTION 903.3.1.2 NFPA 13R SPRINKLER |
| | SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS IN GROUP R |
| | OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN HEIGHT |
| | IN BUILDINGS NOT EXCEEDING 60 FEET (18 288 MM) IN |
| | HEIGHT ABOVE GRADE PLANE SHALL BE PERMITTED TO BE |
| | INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R. |
| | |
| | AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP |
| | TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS |
| | NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE |
| | PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN |
| | ACCORDANCE WITH NFPA 13R. |
| | 8) IN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY PLAN, |
| | JUST A FLOOR PLAN A1.02. THE EXAMINATION OF THE |
| | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE |
| | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE SECTION 503). |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | PRE-ENGINEERED SYSTEMS |
| | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | VERTICAL ACCESSIBILITY |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | |
| | 9) PLEASE PROVIDE AN ITEMIZED LETTER FROM EITHER THE |
| | DESIGNER OF RECORD OR THE CONTRACTOR ON THEIR |
| | LETTERHEAD WHERE 20% OF THEIR BUDGET OR $30,000.00 |
| | DOLLARS WILL BE SPENT IN MAKING ACCESSIBLE UPGRADES TO |
| | THE 1ST FLOOR. PLEASE REVIEW THE FOLLOWING CODE SECTION |
| | IN WHAT ORDER THESE FUNDS ARE TO BE SPENT. |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.2 ACCESSIBLE |
| | FEATURES IN THE EVENT OF DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 9A) PLEASE NOTE CURRENTLY THERE IS NO ACCESSIBLE |
| | ENTRANCE. GOGGLE STREET VIEW SHOWS STEPS AND LANDING TO |
| | THE FRONT DOOR. |
| | |
| | 9B) THE PLANS DO NOT SHOW TRAVEL DISTANCES AND IF A 2ND |
| | EGRESS IS REQUIRED ON THE 1ST FLOOR AND THE VESTIBULE 2 |
| | IS GOING TO BE USED AS THE 2ND REQUIRED EGRESS PLEASE |
| | SHOW ACCOMMODATIONS FOR MANEUVERING OF AMBULANCE |
| | STRETCHERS TO THE EXTERIOR OF THE BUILDING. |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 9C) SHEET A1.02. THE 1ST FLOOR PLAN 1ST FLOOR SHOWS A |
| | TABLE AND CHAIRS LISTED AS 120, AND LISTED STAFF AREA, |
| | WILL ANY OF THE CUSTOMERS AND OR RELATIVE EVER BE ABLE |
| | TO USE THIS AREA FOR EITHER SNACKS OR MEALS? IF SO THEN |
| | COMPLIANCE WILL BE REQUIRED WITH THE 2017 ACCESSIBILITY |
| | CODE SECTIONS: |
| | 9C)(1) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES, |
| | STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY |
| | CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL |
| | GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ABA |
| | SCOPING PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 9C)(2) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 9C)(3) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 10) IMPACT FEES- PAPER SUBMITTALS |
| | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE |
| | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS |
| | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM |
| | |
| | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| 2019-02-05 16:54:46 | NOTES IN ERROR DELETED PV |