| 2019-01-29 10:41:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19010564 |
| | 1/29/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) BASED ON THE BEECH OVEN INSTALLATION INSTRUCTIONS, |
| | AND SECTION 507.2 FBC M, A GREASE EXHAUST HOOD AND FIRE |
| | SUPPRESSION SYSTEM WILL BE REQUIRED FOR THE OVEN- |
| | PLEASE CORRECT THE PLAN ACCORDINGLY. |
| | |
| | 2) THE BEECH PIZZA OVEN, WHICH IS GAS OR WOOD-FIRED, |
| | SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL 2162 |
| | WHICH IS THE LISTING REQUIREMENT FOR SOLID-FUEL-FIRED |
| | OVENS- SECTION 917.1 FBC M. |
| | |
| | 3) REVISE SHEET 9 TO INCLUDE ALL REQUIRED GREASE |
| | EXHAUST DUCT AND FAN COMPLIANCES FOR THE PIZZA HOOD |
| | SYSTEM, INCLUDING THE SLOPE OF THE DUCT, CLEANOUT |
| | LOCATIONS, DUCT WRAPPING ETC.THE NEW HEF-1 FAN SHALL BE |
| | IN COMPLIANCE WITH SECTION 506.5 OR BE UL 762 LISTED |
| | AND LABELED, AND SHALL BE LOCATED IN A ROOM OR SPACE |
| | HAVING THE SAME FIRE-RESISTANCE RATING AS THE DUCT |
| | ENCLOSURE- SECTIONS 506.5.1 AND 506.5.1.2 FBC M. |
| | |
| | 4) PLEASE BIND THE PLANS TOGETHER NEATLY SO SHEETS DO |
| | NOT BECOME LOST OR MISPLACED- SECTION 107.2.1.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |