Plan Review Notes
Plan Review Notes For Permit 19010528
Permit Number 19010528
Review Stop B
Sequence Number 1
Notes
Date Text
2019-02-04 11:02:52****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. FBC B 107 PROVIDE THE N.O.A./PRODUCT APPROVAL FOR
 THE ANGLED MULLION BARS TO BE INSTALLED AT THE FRONT
 BAY WINDOW.
  
 2. FBC R 310.2.1 (EMERGENCY ESCAPE MINIMUM OPENING
 SIZE) THIS CODE REQUIREMENT FOR THE BED ROOM WINDOW
 HEIGHTS WILL NOT COMPLY WITH OUT THE EXCEPTION FROM THE
 EXISTING BUILDING CODE, (SEE ITEM #3 BELOW).
  
 3. FBC EB 702.5 (EMERGENCY ESCAPE AND RESCUE OPENINGS)
 PROVIDE AN EXISTING FLOOR PLAN SHOWING THE BED ROOM
 WINDOWS TO BE CHANGED OUT ARE THE SAME TYPE (SINGLE
 HUNG) THAT WILL BE REPLACED WITH, IN ORDER TO MEET THIS
 CODE EXCEPTION.