2019-06-07 13:44:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE
 COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 2. CORRECTED.
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED IS THE TYPE
 PERMITTED FOR A SINGLE DWELLING UNIT. NEC 220 (LOAD
 CALCULATION STILL NOT CORRECT. WATER HEATER DOES NOT
 MATCH WHAT IS SHOWN IN PANEL SCHEDULE, MATH IS NOT
 CORRECT, BUILDING LOAD SHOWS A WASHER/DRYER BUT THIS IS
 NOT SHOWN ON PLAN OR IN PANEL SCHEDULES, AND SHOULD BE
 INCLUDED IN THE LOAD CALCULATION FOR WHICHEVER PANEL IT
 IS FED FROM. PROVIDE ACCURATE LOAD CALCULATION.)
 4. PROVIDE ACCURATE RISER DIAGRAM. RISER SHOWS ONE
 SERVICE ENTRANCE TO A METER CAN, BUT THE NOTE SAYS THIS
 IS 4 METER CANS. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED. 4 METER CANS CANNOT FEED ONE DISCONNECT. NEC
 215.5; WPB FBC 107.2.1 (NOT CORRECTED. RISER DOES NOT
 MATCH WHAT IS SHOWN ON PLAN.)
 5. SERVICE DROP IS SHOWN TO BE SUPPLIED BY FPL. IF THIS
 CHANGES, A REVISION TO THE PLAN WILL BE NECESSARY. WPB
 FBC 107.2.1
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 (DEFERRED SUBMITTAL ACCEPTED.)
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9 (NOT PROVIDED.)
 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4 (ONLY ONE PANEL SCHEDULE WAS PROVIDED.
 THERE ARE MULTIPLE PANELS. PROVIDE FOR EACH.)(3RD
 REVIEW: THE PANEL SCHEDULES PROVIDED DO NOT MATCH WHAT
 IS SHOWN ON FLOOR PLAN. WHERE IS THE PANEL SCHEDULE FOR
 THE OUTSIDE METER/MAIN? ARE ANY ITEMS FED FROM THIS?)
 11. CORRECTED.
 12. CORRECTED.
 13. RISER DIAGRAM AND PLAN HAS SEVERAL DISCREPANCIES AS
 TO PANEL SIZE. SOME AREAS SHOW 100 AMP PANELS, ANOTHER
 AREA SHOWS 125 AMP PANELS, ANOTHER SHOWS 150 AMP
 PANELS, AND ONE SHOWS A 200 AMP PANEL. CORRECT
 DISCREAPNCIES. WPB FBC 107.2.1 (PLAN AND RISER STILL DO
 NOT MATCH.)
  
 NEW COMMENTS:
  
 14. FOR EACH DWELLING UNIT OF A MULTIFAMILY DWELLING
 WHERE THE DWELLING UNIT IS LOCATED AT GRADE LEVEL AND
 PROVIDED WITH INDIVIDUAL EXTERIOR ENTRANCE/EGRESS, AT
 LEAST ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM
 GRADE AND NOT MORE THAN 2.0 M (61?2 FT) ABOVE GRADE
 LEVEL SHALL BE INSTALLED. PROVIDE CORRECTION. NEC
 210.52(E)(2)
 15. SHOW LOCATION ON PLAN OF A/C UNITS AND PROVIDE A
 GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER