| 2019-06-07 13:44:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE |
| | COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 (NOT PROVIDED.) |
| | 2. CORRECTED. |
| | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. THE LOAD CALCULATION PROVIDED IS THE TYPE |
| | PERMITTED FOR A SINGLE DWELLING UNIT. NEC 220 (LOAD |
| | CALCULATION STILL NOT CORRECT. WATER HEATER DOES NOT |
| | MATCH WHAT IS SHOWN IN PANEL SCHEDULE, MATH IS NOT |
| | CORRECT, BUILDING LOAD SHOWS A WASHER/DRYER BUT THIS IS |
| | NOT SHOWN ON PLAN OR IN PANEL SCHEDULES, AND SHOULD BE |
| | INCLUDED IN THE LOAD CALCULATION FOR WHICHEVER PANEL IT |
| | IS FED FROM. PROVIDE ACCURATE LOAD CALCULATION.) |
| | 4. PROVIDE ACCURATE RISER DIAGRAM. RISER SHOWS ONE |
| | SERVICE ENTRANCE TO A METER CAN, BUT THE NOTE SAYS THIS |
| | IS 4 METER CANS. PROVIDE CLARIFICATION AND CORRECTIONS |
| | AS NEEDED. 4 METER CANS CANNOT FEED ONE DISCONNECT. NEC |
| | 215.5; WPB FBC 107.2.1 (NOT CORRECTED. RISER DOES NOT |
| | MATCH WHAT IS SHOWN ON PLAN.) |
| | 5. SERVICE DROP IS SHOWN TO BE SUPPLIED BY FPL. IF THIS |
| | CHANGES, A REVISION TO THE PLAN WILL BE NECESSARY. WPB |
| | FBC 107.2.1 |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 |
| | (DEFERRED SUBMITTAL ACCEPTED.) |
| | 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. |
| | NEC 110.3, 110.9 (NOT PROVIDED.) |
| | 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR |
| | ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| | TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, |
| | 215.5, 408.4 (ONLY ONE PANEL SCHEDULE WAS PROVIDED. |
| | THERE ARE MULTIPLE PANELS. PROVIDE FOR EACH.)(3RD |
| | REVIEW: THE PANEL SCHEDULES PROVIDED DO NOT MATCH WHAT |
| | IS SHOWN ON FLOOR PLAN. WHERE IS THE PANEL SCHEDULE FOR |
| | THE OUTSIDE METER/MAIN? ARE ANY ITEMS FED FROM THIS?) |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. RISER DIAGRAM AND PLAN HAS SEVERAL DISCREPANCIES AS |
| | TO PANEL SIZE. SOME AREAS SHOW 100 AMP PANELS, ANOTHER |
| | AREA SHOWS 125 AMP PANELS, ANOTHER SHOWS 150 AMP |
| | PANELS, AND ONE SHOWS A 200 AMP PANEL. CORRECT |
| | DISCREAPNCIES. WPB FBC 107.2.1 (PLAN AND RISER STILL DO |
| | NOT MATCH.) |
| | |
| | NEW COMMENTS: |
| | |
| | 14. FOR EACH DWELLING UNIT OF A MULTIFAMILY DWELLING |
| | WHERE THE DWELLING UNIT IS LOCATED AT GRADE LEVEL AND |
| | PROVIDED WITH INDIVIDUAL EXTERIOR ENTRANCE/EGRESS, AT |
| | LEAST ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM |
| | GRADE AND NOT MORE THAN 2.0 M (61?2 FT) ABOVE GRADE |
| | LEVEL SHALL BE INSTALLED. PROVIDE CORRECTION. NEC |
| | 210.52(E)(2) |
| | 15. SHOW LOCATION ON PLAN OF A/C UNITS AND PROVIDE A |
| | GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC |
| | 210.63; FBC RE E3901.12 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |