Plan Review Notes
Plan Review Notes For Permit 19010525
Permit Number 19010525
Review Stop E
Sequence Number 2
Notes
Date Text
2019-05-15 13:13:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 2. CORRECTED.
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED IS THE TYPE
 PERMITTED FOR A SINGLE DWELLING UNIT. NEC 220 (NOT
 CORRECT. THERE ARE TWO LOAD CALCULATIONS, BUT THEY ARE
 IDENTICAL AND BOTH MARKED UNIT 1. THERE IS NO LOAD
 CALCULATION FOR THE ENTIRE SERVICE.)
 4. PROVIDE ACCURATE RISER DIAGRAM. RISER SHOWS ONE
 SERVICE ENTRANCE TO A METER CAN, BUT THE NOTE SAYS THIS
 IS 4 METER CANS. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED. 4 METER CANS CANNOT FEED ONE DISCONNECT. NEC
 215.5; WPB FBC 107.2.1 (NOT CORRECTED. RISER SHOWS ONE
 METER WITH 2 PANELS, BUT THE PLAN SHOWS AT LEAST 3
 PANELS. CORRECT DISCREPANCIES.)
 5. WIRE SIZE SHOWN IN SERVICE DROP IS NOT ADEQUATELY
 SIZED TO HANDLE THE LOAD STATED. PROVIDE CORRECTION.
 NEC 310.15(B)(16) (NOT CORRECTED.)
 6. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1(NOT PROVIDED.)
 7. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2
 AS APPLICABLE. (NOT PROVIDED.)
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 (NOT
 PROVIDED.)
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9 (NOT PROVIDED.)
 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4 (ONLY ONE PANEL SCHEDULE WAS PROVIDED.
 THERE ARE MULTIPLE PANELS. PROVIDE FOR EACH.)
 11. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12 (NOT CORRECTED.)
  
 NEW COMMENTS:
  
 12. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 13. RISER DIAGRAM AND PLAN HAS SEVERAL DISCREPANCIES AS
 TO PANEL SIZE. SOME AREAS SHOW 100 AMP PANELS, ANOTHER
 AREA SHOWS 125 AMP PANELS, ANOTHER SHOWS 150 AMP
 PANELS, AND ONE SHOWS A 200 AMP PANEL. CORRECT
 DISCREAPNCIES. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  