| 2019-02-20 08:30:22 | |
| | 1ST REVIEW: 19010515 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE PRIVATE BATHROOM DOES NOT MEET THE EXEMPTION FOR |
| | A SINGLE OCCUPANT ACCESSED ONLY THROUGH A PRIVATE |
| | OFFICE IT SHALL MEET ALL THE REQUIREMENTS OF THE FBC |
| | ACC CH 6 |
| | 2. THE SHOWER DIMENSIONS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING FBC ACC 608.2.1, 608.2.2, 608.2.3 |
| | 3. THE CONTROLS SHALL COMPLY WITH THE REQUIREMENTS OF |
| | THE TYPE OF SHOWER. FBC ACC 608.5.1, 608.5.2, 608.5.3 |
| | 4. PLEASE NOTE ON THE PLAN OR SHOW ON WATER ISOMETRIC A |
| | BACKFLOW IS REQUIRED ON THE WATER FILTER , REFRIGERATOR |
| | ICE MAKER AND COFFEE MAKER .PER FBC PL 608.3, 608.16.10 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |