Plan Review Notes
Plan Review Notes For Permit 19010515
Permit Number 19010515
Review Stop P
Sequence Number 1
Notes
Date Text
2019-02-20 08:30:22 
 1ST REVIEW: 19010515
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE PRIVATE BATHROOM DOES NOT MEET THE EXEMPTION FOR
 A SINGLE OCCUPANT ACCESSED ONLY THROUGH A PRIVATE
 OFFICE IT SHALL MEET ALL THE REQUIREMENTS OF THE FBC
 ACC CH 6
 2. THE SHOWER DIMENSIONS SHALL COMPLY WITH ONE OF THE
 FOLLOWING FBC ACC 608.2.1, 608.2.2, 608.2.3
 3. THE CONTROLS SHALL COMPLY WITH THE REQUIREMENTS OF
 THE TYPE OF SHOWER. FBC ACC 608.5.1, 608.5.2, 608.5.3
 4. PLEASE NOTE ON THE PLAN OR SHOW ON WATER ISOMETRIC A
 BACKFLOW IS REQUIRED ON THE WATER FILTER , REFRIGERATOR
 ICE MAKER AND COFFEE MAKER .PER FBC PL 608.3, 608.16.10
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  