| Plan Review Notes For Permit 19010507 |
| Permit Number |
19010507 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-01-18 10:06:34 | PERMIT # 19010507 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED PROVISO: | | | | | | 1) SHEET A0.15 - REFERENCE IS MADE REGARDING THE | | | ADDITION OF MAGLOCKS ON THE MAIN ENTRY DOOR. PLEASE | | | REVIEW AND ENSURE COMPLIANCE WITH ANY AND ALL | | | APPLICABLE REQUIREMENTS AS OUTLINED IN NFPA 101, | | | CHAPTER 7. | | | | | | 2) A SEPARATE PERMIT WILL BE REQUIRED IF | | | ACCESS-CONTROLLED EGRESS WILL BE INSTALLED. | | | | | | 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | | | 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|