| 2019-01-30 07:02:01 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19010507 |
| | ADD: 4631 N. CONGRESS AVE. SUITE: 101 |
| | CONT: CONENGINEERS BUILDERS LLC |
| | TEL: 954-849-7322 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 30/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) THE LIFE SAFETY SHEET DOES NOT PROVIDE ANY OF THE |
| | CODE REQUIREMENTS AS TO WHAT CODE THE PLANS WERE |
| | CREATED, NOR DOES THE PLAN INDICATE UNDER THE EXISTING |
| | BUILDING CODE WHICH METHOD THE PLANS WERE DEVELOPED NOR |
| | DOES THE PLAN INDICATE ANY OF THE BUILDING CRITERIA. |
| | |
| | 1A) THE 2017 FBC-B WAS ADOPTED STATEWIDE ON DEC. |
| | 30/2017. |
| | |
| | 1B) THE 2017 FBC-EXISTING BUILDING CODE SECTION 301.1. |
| | THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION |
| | OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 |
| | THROUGH 301.1.3 AS SELECTED BY THE APPLICANT. SECTIONS |
| | 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED IN |
| | COMBINATION WITH EACH OTHER. |
| | |
| | 1C) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING: |
| | 1C)(2.) MINIMUM TYPE OF CONSTRUCTION SHALL BE |
| | DETERMINED (SEE SECTION 503). |
| | 1C)(3.) IS THE BUILDING FIRE SPRINKLERED OR NOT? IT |
| | APPEARS THAT TRAVEL DISTANCES WERE TAKEN FOR SPRINKLERS |
| | W/ TABLE 1006.2.1. NO FIRE SPRINKLER PLANS WERE FILED |
| | WITH THIS PERMIT? |
| | |
| | 2) SHEET 013 A1.12 THE DIMENSION PLAN IT APPEARS THAT |
| | THE RESTROOM 114 AND OFFICE 113 BOTH ARE MISSING THE |
| | WIDTH AND LENGTH OF THE ROOMS, THE TELCO ROOM 115 AND |
| | STORAGE ROOM 112 ARE MISSING THE WIDTH OF THE ROOMS. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED TO BE ABLE |
| | TO BUILD THE WALLS WITHOUT DIMENSIONS. |
| | |
| | 3) SHEET 020-A5.51 MILLWORK DETAILS DETAIL NUMBER 2 |
| | INDICATES THE BREAKROOM COUNTER TOP AND SINK, WHAT THE |
| | PLAN DOES NOT PROVIDE IS AT WHAT HEIGHT THE COUNTER TOP |
| | OR SINK IS. THE PLAN STATES REFER TO PLANS. SHEET |
| | 012-A1.11 DOES SHOW WHERE TO FIND DETAILS FOR THE |
| | RECEPTIONIST DESK, EXAM ROOM SINKS BUT THERE IS NO |
| | DETAIL OR CUT SECTION FOR THE BREAK ROOM SINK. PLEASE |
| | SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE |
| | SECTION: |
| | 606.3HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |