2019-01-28 15:29:46REVISION
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A REVISED SURVEY THAT DETAILS THE CHANGES
 FROM THE ONE THAT WAS SUBMITTED. THE REVISED SCOPE OF
 WORK FOR THE COVERED PATIO AND POOL DECKING NEEDS TO
 CLEARLY INDICATE THE NEW SCOPE OF WORK. ITEM (D) ON THE
 APPROVED SCOPE OF WORK SPECIFES A CHILD SAFETY FENCE
 AND ITEM (E) SPECIFIES YARD FENCING IN THE NEW
 LANDSCAPE HEDGE SURROUNDING POOL. SPECIFY HOW THE CHILD
 BARRIER WILL BE INSTALLED WITHOUT A DECK. FBC 107.2.1 &
 FBC-R 4501.17
  
 2) THE DOOR AND WINDOW ALARMS ARE REQUIRED TO COMPLY
 WITH UL 2017 AND FBC-R 4501.17.1.9. THE ALARM DOCUMENTS
 THAT WERE SUBMITTED DO NOT SPECIFY COMPLIANCE WITH UL
 2017.
  
 3) THE DOOR AND WINDOW ALARMS ARE REQUIRED IN
 CONJUNCTION WITH A REQUIRED EXTERIOR BARRIER FENCE. THE
 ALARM IS THE BARRIER BETWEEN THE OWNER'S HOUSE AND THE
 POOL AND THE FENCE IS THE BARRIER FROM THE NEIGHBORS'
 HOUSES AND THE POOL. FBC-R 4501.17.1.9
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  