2019-05-08 18:41:46PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIGNED AND SEALED ENGINEERING THAT WAS SUBMITTED
 FOR THE DIVERSITECH PADS IS LIMITED TO GENERAC
 GENERATORS WITH SPECIFIC DIMENSIONS AND WEIGHT. SEE
 LIMITS AND REQUIREMENTS OF USE ON PAGE 1 OF THE
 DOCUMENTS. IN ORDER TO USE THESE PADS FOR THE POOL
 HEATERS, YOU WILL HAVE TO PROVIDE A COMPARATIVE
 ANALYSIS TO SHOW THAT THE DIMENSIONS, WEIGHT AND
 ANCHORING ARE EQUAL TO THE GENERATOR THAT THE PAD IS
 DESIGNED FOR. YOU WILL ALSO NEED TO SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS FOR THE POOL HEATER WITH
 ITS DIMENSIONS AND WEIGHT SPECIFIED. FBC 1609.1, FBCM
 301.15
 ALTERNATELY, YOU CAN FORM AND POUR A 4" CONCRETE SLAB
 IN PLACE. YOU WILL HAVE TO SUBMIT A DRAWING SHOWING THE
 DIMENSIONS OF THE SLAB WITH WIRE MESH OF FIBER-MESH
 CONCRETE. YOUR NAME AND SIGNATURE AND THE ADDRESS OF
 THE PROJECT IS REQUIRED ON THE DRAWINGS.