| 2019-05-31 14:10:13 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19010393 | | | 5/31/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET ME-1: SHOW THE EXACT LOCATION OF THE AC | | | CONDENSER AND PROVIDE ENGINEERED DETAILS FOR | | | INSTALLATION- SECTIPON 301.15 FBC M. | | | | | | 2) ME-1: PROVDE A SEQUENCE OF OPERATION FOR THE OUTSIDE | | | AIR FAN. WILL THE FAN BE ELECTRICALLY LINKED WITH THE | | | AIR HANDLER FOR AUTOMATIC OPERATION? | | | | | | 3) ME-1: PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION | | | 307.2.1 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|