| 2019-04-18 15:26:12 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19010393 | | | 4/18/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ME-1: THE OUTDOOR AIR TABLE IS INCORRECT. REFER TO | | | TABLE 403.3.1.1 FBC M: OUTDOOR AIR FOR FAST FOOD IS | | | CALCULATED AT 100 PERSONS PER 100 S.F. (23 PERSONS/7.5 | | | CFMS PER PERSON= 172.5 CFMS ) + (0.18 CFMS/232 SF.= 42) | | | = 215 CFMS OF OUTSIDE AIR REQUIRED. PLEASE CORRECT THE | | | TABLE THAT INDICATES 98.4 CFMS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|