Plan Review Notes For Permit 19010393
Permit Number 19010393
Review Stop B
Sequence Number 2
Notes
Date Text
2019-05-08 14:48:54***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING 2ND REVIEW DENIED:
  
 1. OK
 2. FAIL, SHEET A-1 UNDER CODE SUMMARY BUILDING CODE 2.4
 LEVELS OF ALTERATION - LEVEL III ALTERATION IS
 INCORRECT.
 PLEASE NOTE, THIS IS A NEW HIGHRISE BUILDING WITH THE
 1ST FLOOR BEING BUILT AS A SHELL SPACE, THIS IS NOT TO
 BE REVIEWED UNDER THE EXISTING BUILDING CODE, SINCE
 THIS WILL BE THE FIRST OCCUPANCY FOR THIS SPACE.
 3. OK
 4. FAIL, SHEET A-1 UNDER DESIGN WIND PRESSURES
 (NEGATIVE PRESSURE), NEEDS TO BE CLEARLY ADDED TO
 REVISED PLAN.
 5. OK
 6. OK
 7. OK
 8. OK
 9. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE
 REVISION AND REMOVE ANY VOIDED SHEETS AND REPLACE AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OFTHE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
  
  