2019-01-30 16:13:33 
 1ST REVIEW: 19010393
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE TEMPERED WATER AT THE LAVATORY SHALL BE
 DELINERED BY A TEMPERATURE LIMITING DEVICE CONFORMING
 WITH ASSE 1070/ CSA B125.3.PER FBC PL 416.5
  
 2. PROVIDE WATER VALVES AT EACH DROP ON THE WATER
 ISOMETRIC DRAWING. PER FBC PL 606.1(5)
  
 3. THE HAND SINK CUP WASHER AND FLOOR DRAIN IN THE
 EMPLOYEE SERVICE AREA SHALL BE CONNECTED TO GREASE
 INTERCEPTOR.PER FBC PL 1003.3.1
  
 4. PROVIDE A GREASE TRAP SIZING CALCULATION FROM THE
 MANUFACTURE FOR SCHIER YOU CAN CONTACT LEE SCHNEEWEISS
 @ 1-800-538-4792 IT SHOULD INCUDE THE FLOOR SINK FOR
 THE MIXER AND FLOOR SINK IN PREP ROOM AND THE FIXTURES
 IN THE EMPLOYEE SERVICE AREA. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  