2019-02-03 10:44:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. NOTE ON PLAN STATES EMERGENCY AND EXIT LIGHTS ARE
 REQUIRED TO BE FED FROM THE GENERAL LIGHTING CIRCUIT IN
 THE AREA, BUT THE LIGHTING PLAN SHOWS THEM FED FROM
 OTHER CIRCUITS. PROVIDE CORRECTION. NEC 700.12(F)
 3. PROVIDE SHOW WINDOW RECEPTACLE PER CODE. IT IS
 LISTED IN PANEL SCHEDULE BUT NOT SHOWN ON PLAN. NEC
 210.62
 4. SIGN CIRCUIT SHOWN ON PANEL SCHEDULE, BUT NOT ON
 PLAN. PROVIDE CORRECTION. NEC 600.5; WPB FBC 107.2.1
 5. RISER DIAGRAMS STATES THERE IS A 400 AMP SINGLE
 PHASE PANEL THAT IS EXISTING. LIGHTING AND POWER PLAN
 SHOW A 200 AMP PANEL EXISTING. PROVIDE CLARIFICATION
 AND/OR CORRECTIONS. WPB FBC 107.2.1; NEC 215.5
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 7. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THREE PHASE LOADS WOULD NOT HAVE
 ALL OF THE LOAD ON ONE PHASE AND NONE ON THE OTHERS.
 LOAD CALCULATION SHOULD INCLUDE 100% OF NON-CONTINUOUS
 LOADS AND 125% OF CONTINUOUS LOADS. NEC 215.2, 220,
 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved