Date Text
2019-01-22 14:18:282017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010393
 ADD: 333 FERN ST. SUITE: 118
 CONT: BELA VISTA CONTRACTORS, INC.
 TEL: 9544-644-3121
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 22 / 2019
 ACTION: DENIED
  
 1) SHEET A-1 AT THE TOP PORTION OF THIS SHEET THE SCOPE
 OF WORK LIST THE ADDRESS OF 7070 SEMINOLE PRATT WHITNEY
 ROAD SUITE # 2 LOXAHATCHEE, FL. THE BOTTOM HALF OF THE
 SHEET UNDER THE HEADING OF GENERAL NOTES LIST THE
 PROJECT LOCATED AT 333 FERN ST. WEST PALM BEACH, FL.
 THE PERMIT APPLICATION ALSO LIST THE
 ADDRESS OF 333 FERN ST. SUITE # 118. DISCREPANCY IN THE
 LOCATION OF WHERE THE WORK IS TO BE COMPLETED UNDER
 THIS PERMIT. 7070 SEMINOLE PRATT WHITNEY ROAD SUITE # 2
 LOXAHATCHEE, FL. IS NOT IN THE CITY LIMITS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A-1 UNDER THE HEADING CODE SUMMARY 1.0
 APPLICABLE CODES:
 APPLICABLE CODES 1.1 LIST THE ALTERATION AS A LEVEL II
 ALTERATION, WHEREAS UNDER THE NOTE 2.4 THE LEVEL OF THE
 ALTERATION AS A LEVEL III ALTERATION. DISCREPANCY IN
 LEVEL OF ALTERATION, 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED. PLEASE NOTE THIS IS A NEW HIGHRISE
 BUILDING WITH THE 1ST FLOOR BEING BUILT AS SHELL SPACE,
 THIS IS NOT TO BE REVIEWED UNDER THE EXISTING BUILDING
 CODE, SINCE WILL BE 1ST OCCUPANCY FOR THIS SPACE!!!
  
 3) SHEET A-1 UNDER THE HEADING BUILDING CODE LIST THIS
 BUILDING AS CONSTRUCTION TYPE III- UNPROTECTED/
 UNSPRINKLERED. PLEASE STOP BY THE JOBSITE, THIS IS A 20
 STORY HIGHRISE BUILDING, PLEASE CORRECT THE BUILDING
 TYPE AND THE BUILDING IS FIRE SPRINKLERED. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET A-1 THE WIND DESIGN INFORMATION GIVEN IS THE
 EXISTING BUILDING IS, THAN 19 FEET TALL, PLEASE
 CORRECT. THIS IS A 20 STORY HIGHRISE BUILDING. PLEASE
 ALSO CORRECT THE NEGATIVE PRESSURES, THEY ARE TAKEN
 FROM THE ROOF LEVEL, SEE ASCE 7-10, CHAPTER 30.
  
 5) SHEET A-5 LIST THE TOILET ACCESSORY SCHEDULE UNDER
 THE 2014 FBC. PLEASE NOTE THE 2017 FBC-ACCESSIBILITY
 CODE WENT INTO EFFECT ON DECEMBER 31, 2017, STATEWIDE,
 PLEASE UPDATE PLAN NOTES.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET A-2 IS THE DIMENSIONED FLOOR PLAN. PLEASE
 REVIEW THE CORRIDOR THAT LEEDS TO THE ACCESSIBLE
 RESTROOM. IT IS DIMENSIONED 3 FOOT 4 INCHES IN WIDTH.
 PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE 404.2.3
 AND FIGURE 404.2.1(H) THAT REQUIRES THE CORRIDOR TO BE
 48 INCHES IN WIDTH.
  
 7) SHEET A-2 DOES NOT INDICATE THE FRONT ENTRY DOOR IF
 THE SIDEWALK IS THE SAME LEVEL AS THE FINISH FLOOR IN
 THE INTERIOR, PLEASE SHOW COMPLIANCE WITH THE 22017
 FBC-ACCESSIBILITY CODE SECTION 402.2 COMPONENTS.
 ACCESSIBLE ROUTES SHALL CONSIST OF ONE OR MORE OF THE
 FOLLOWING COMPONENTS: WALKING SURFACES WITH A RUNNING
 SLOPE NOT STEEPER THAN 1:20, DOORWAYS, RAMPS, CURB
 RAMPS EXCLUDING THE FLARED SIDES, ELEVATORS, AND
 PLATFORM LIFTS. ALL COMPONENTS OF AN ACCESSIBLE ROUTE
 SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
 CHAPTER 4 AND 208.3.1.
  
 8) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: HT
 TP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTF
 EES/FORMS/QUESTIONNAIRE.PDF
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved