2019-03-16 06:33:18MECHANICAL PLAN REVIEW FAIL
  
  
  
 1. FBC ENERGY SECTION R 103.1.1.2 THE SUBMITTED
 DOCUMENTS FOR ENERGY CALCULATIONS NEED TO BE SIGNED BY
 THE OWNER/AGENT.
 2. FBC RESIDENTIAL M1602.3 THE RETURN AIR DUCTS DO NOT
 MEET THE REQUIRED SIZE, CONSIDERING THE SIZE OF SUPPLY
 DUCTS, AT THE ROOMS OF THE SECOND FLOOR.
 PASS THROUGH RETURNS SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) PER 2017 -
 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION PER
 SECTION M1602.3BALANCED RETURN AIR.
 PLAN DENIED
  