| 2019-03-16 06:33:18 | MECHANICAL PLAN REVIEW FAIL | | | | | | | | | | | | 1. FBC ENERGY SECTION R 103.1.1.2 THE SUBMITTED | | | DOCUMENTS FOR ENERGY CALCULATIONS NEED TO BE SIGNED BY | | | THE OWNER/AGENT. | | | 2. FBC RESIDENTIAL M1602.3 THE RETURN AIR DUCTS DO NOT | | | MEET THE REQUIRED SIZE, CONSIDERING THE SIZE OF SUPPLY | | | DUCTS, AT THE ROOMS OF THE SECOND FLOOR. | | | PASS THROUGH RETURNS SHALL USE 50 SQUARE INCHES (OF | | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) PER 2017 - | | | FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION PER | | | SECTION M1602.3BALANCED RETURN AIR. | | | PLAN DENIED | | | | | | CHRIS MONTELLO | | | 805-6733 |
|