| Notes |
| Date |
Text |
| 2019-01-24 13:18:29 | CODES IN EFFECT: | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 5TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | PLUMBING COMMENTS: DENIED | | | | | | 1. RE: PLAN SHEET A-5.0; PLUMBING DIAGRAM | | | A. CLOTHES WASHER DRAIN SHALL NOT CONNECT TO BATHROOM | | | GROUP WET VENT PER FBC RES P3108.1. CONNECT DOWNSTREAM | | | TO COMPLY. | | | B. 3" RISER SHALL BE LABELED "SOIL STACK", NOT "VENT" | | | PER WPB FBC 107.2.1. | | | 2.PROVIDE MANUFACTURER'S SPECIFICATION TO INCLUDE THE | | | GPM AND ELECTRICAL CHARACTERISTICS FOR THE TANKLESS | | | WATER HEATERS PER WPB FBC 107.2.1 AND CONFIRM THEY WILL | | | SUPPLY THE HOT WATER DEMAND. | | | | | | SINCERELY, | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | 561-805-6715 | | | [email protected] |
|