Plan Review Notes
Plan Review Notes For Permit 19010367
Permit Number 19010367
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-22 08:46:27****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 AFTER RESEARCHING INFORMATION FROM THE LAST
 PERMIT(18090367) RELATING TO INTERIOR RENOVATION WORK
 AT THIS ADDRESS, NO INFORMATION ON FLOORING
 UNDERLAYMENT WAS FOUND.
 IT APPEARS THAT THE ORIGINAL INTENTION OF THIS PLAN,
 PER NOTE 7 OF PAGE A-1, WAS TO HAVE AN APPROVED
 FLOORING UNDERLAYMENT AS REQUIRED BY THE FLORIDA
 BUILDING CODE.
 PLEASE PROVIDE A TESTED AND APPROVED SUBMITTAL(SUCH AS
 PROFLEX SUPER SIM 90) FOR THE UNDERLAYMENT AS NOTED
 BELOW FROM THE LAST PLAN REVIEW:
  
 1 SHEET A?1 NOTE # 7 INDICATES THE USE OF PROFLEX MSC
 MEGA SOUND CONTROL MEMBRANE AS THE FLOOR INSULATION TO
 BE INSTALLED. PLEASE NOTE TO DATE THE CITY HAS NOT
 RECEIVED A CODE COMPLIANT TEST FOR THIS PRODUCT. WHAT
 WE HAVE SEEN FOR OF PROFLEX MSC MEGA SOUND CONTROL IS
 FOR A 8 INCH SLAB, WITH A DROPPED CEILING WITH
 INSULATION IN THE DROPPED CEILING. PLEASE SUBMIT TEST
 FOR THIS PRODUCT. PLEASE NOTE WE DO HAVE TEST FOR
 PROFLEX SUPER SIM 90 WITH A IIC OF 50, STC OF 52 AND
 FLAME SPREAD AND SMOKE DEVELOPMENT OF 0 ON A 6 INCH
 CONCRETE SLAB.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC?B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 1A) FBC?B 2017 1207.3 STRUCTURE?BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 1B) FBC?B 2017 1207.2 AIR?BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR?BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 1C) FLAME SPREAD? FBC?B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  