| 2019-02-22 08:46:27 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | AFTER RESEARCHING INFORMATION FROM THE LAST |
| | PERMIT(18090367) RELATING TO INTERIOR RENOVATION WORK |
| | AT THIS ADDRESS, NO INFORMATION ON FLOORING |
| | UNDERLAYMENT WAS FOUND. |
| | IT APPEARS THAT THE ORIGINAL INTENTION OF THIS PLAN, |
| | PER NOTE 7 OF PAGE A-1, WAS TO HAVE AN APPROVED |
| | FLOORING UNDERLAYMENT AS REQUIRED BY THE FLORIDA |
| | BUILDING CODE. |
| | PLEASE PROVIDE A TESTED AND APPROVED SUBMITTAL(SUCH AS |
| | PROFLEX SUPER SIM 90) FOR THE UNDERLAYMENT AS NOTED |
| | BELOW FROM THE LAST PLAN REVIEW: |
| | |
| | 1 SHEET A?1 NOTE # 7 INDICATES THE USE OF PROFLEX MSC |
| | MEGA SOUND CONTROL MEMBRANE AS THE FLOOR INSULATION TO |
| | BE INSTALLED. PLEASE NOTE TO DATE THE CITY HAS NOT |
| | RECEIVED A CODE COMPLIANT TEST FOR THIS PRODUCT. WHAT |
| | WE HAVE SEEN FOR OF PROFLEX MSC MEGA SOUND CONTROL IS |
| | FOR A 8 INCH SLAB, WITH A DROPPED CEILING WITH |
| | INSULATION IN THE DROPPED CEILING. PLEASE SUBMIT TEST |
| | FOR THIS PRODUCT. PLEASE NOTE WE DO HAVE TEST FOR |
| | PROFLEX SUPER SIM 90 WITH A IIC OF 50, STC OF 52 AND |
| | FLAME SPREAD AND SMOKE DEVELOPMENT OF 0 ON A 6 INCH |
| | CONCRETE SLAB. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC?B |
| | 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 1A) FBC?B 2017 1207.3 STRUCTURE?BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | 1B) FBC?B 2017 1207.2 AIR?BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR?BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | 1C) FLAME SPREAD? FBC?B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |