| Plan Review Notes For Permit 19010315 |
| Permit Number |
19010315 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-18 10:07:46 | PLUMBING 2ND REVIEW**DENIED** | | | | | | 1) THE WASHING MACHINE SHALL BE MIN 3" TO THE BRANCH OR | | | STACK. FBC P406.2 | | | | | | 2) BOTH BATHROOM ISOMETRIC SHOW 2 WET VENTED FIXTURE | | | PAST THE VENT. ONLY 1 WET VENTED FIXTURE IS PERMITTED | | | PAST BEYOND THE VENT. FBC-R P 3108.2.1 | | | | | | 3) ADD NOTE TO PLAN ALL HOT WATER PIPING SHALL BE | | | INSULATED WITH MIN R-3 VALUE INSULATION. FBC-ENERGY | | | R403.5.3 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|