| 2019-06-27 13:50:31 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL |
| | REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | ***ENERGY CALCUATIIONS NEED TO BE CERTIFIED BY THE |
| | OWNER PRIOR TO APPROVE THE MECHANICAL REVIEW. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1-PROVIDE COMPLETE MECHANICAL PLANS AND EQUIPMENT |
| | SIZING CALCULATIONS OR PROVIDE COMPLETE INFORMATION |
| | UNDER A SEPARATE APPLICATION. SEC. 107.5.3(11) CITY |
| | AMENDMENTS. |
| | NOTE: |
| | NO MECHANICAL PLANS WERE SUBMITTED AND THE EQUIPMENT |
| | SIZING CALCULATIONS SUBMITTED ARE FOR ANOTHER PROJECT. |
| | |
| | RESPONSE: |
| | A) EQUIPMENT SHOWN ON A/C PLAN PROVIDED DOESN'T MATCH |
| | EQUIPMENT LISTED ON THE LOAD CALCULATIONS SUBMITTED. |
| | REVISE AS REQUIRED TO MATCH. SEC. R403.7.1 FBC-ENERGY |
| | CONSERVATION. |
| | NOTE: ALSO COORDINATE WITH A/C SEER SHOWN ON THE ENERGY |
| | CALCULATIONS TO AVOID CONFLICTS/DELAYS. |
| | |
| | B) A/C PLAN SUBMITTED DOESN'T SHOW THE MAIN RETURN AIR |
| | OPENING. SEC. M1602.2 FBC-RESIDENTIAL. SPECIFY SIZE AND |
| | LOCATION |
| | |
| | C) CFM'S SHOWN ON THE A/C PLAN DON'T MATCH CFM'S SHOWN |
| | ON THE LOAD CALCULATIONS. REVISE AS REQUIRED TO MATCH. |
| | . SEC. R403.7.1 FBC-ENERGY CONSERVATION. |
| | |
| | |
| | 2- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR |
| | REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW |
| | COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |