| 2019-02-04 16:50:59 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PLEASE CONTACT MIKE ORIO CITY OF WEST PALM BEACH GIS |
| | SUPPORT SPECIALIST TO GET APPROVED ADDRESS. |
| | SEE CONTACT INFORMATION BELOW. |
| | |
| | CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ |
| | INFORMATION TECHNOLOGY |
| | TEL: 561-494-1040 |
| | E-MAIL: [email protected] |
| | |
| | 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | FBC R 401.3 (DRAINAGE) |
| | FBC 107.2.5 (SITE PLAN) |
| | FBC 110.9 (IMPACT OF CONSTRUCTION) |
| | |
| | 3- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC. R101.5 |
| | FBC-ENERGY CONSERVATION. NOTE: CALCULATIONS SUBMITTED |
| | ARE FOR ANOTHER ADDRESS (THEREFORE, THEY WERE NOT |
| | REVIEWED) AND TOO OLD. NEW CALCULATIONS FOR CORRECT |
| | ADDRESS AND WITH CURRENT CODE (2017) |
| | |
| | 4- ARCHITECT OF RECORD TO SPECIFY ON PLANS INSULATION R |
| | VALUE FOR EXTERIOR WALLS, ADJACENT WALLS BETWEEN GARAGE |
| | AND A/C AREA AND CEILING AS REQUIRED BY SEC. R103.2 |
| | FBC-ENERGY CONSERVATION. |
| | NOTE: ENERGY CALCULATIONS AND PLANS TO BE COORDINATED |
| | TO AVOID CONFLICTS/DELAYS. |
| | |
| | 5- SOIL TEST REPORT SUBMITTED: |
| | A)REPORT SUBMITTED IS PRELIMINARY AND DOESN'T PROVIDE |
| | ENOUGH INFORMATION. SEE SEC. 1803.6 FBC AND PROVIDE |
| | COMPLETE REPORT SHOWING ALL THE RELEVANT INFORMATION. |
| | SOIL BEARING CAP CITY, SOIL PREPARATION, FOOTINGS |
| | RECOMMENDATION, EXPECTED SETTLEMENT, , ETC. |
| | |
| | B) PROVIDE REPORT WITH ENGINEER'S ORIGINAL SEAL AND |
| | SIGNATURE (2 COPIES) AS REQUIRED BY CHAPTER 471 F.S. |
| | WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 6- A)DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON THE |
| | EXTERIOR ELEVATIONS ON SHEET A5 DON'T CORRESPOND TO |
| | DESIGN PRESSURES FOR BUILDING EXPOSURE "C". REVISE AS |
| | REQUIRED. SEC. R301.2.1.4 FBC-RESIDENTIAL. NOTE: |
| | PROVIDE DESIGN PRESSURES BASED ON THE TRIBUTARY AREA |
| | AND END ZONE OR INTERIOR ZONE. |
| | |
| | B) REVISE ROOF AND WALL DESIGN PRESSURES SHOWN ON THE |
| | WIND LOAD SCHEDULE ON SHEET A3. THEY DON'T CORRESPOND |
| | TO A BUILDING IN EXPOSURE "C". REVISE AS REQUIRED. SEC. |
| | R301.2.1.4 FBC-RESIDENTIAL. |
| | |
| | 7- NOTE #2 OF THE GENERAL NOTES AND NOTE #2 BELOW |
| | WINDOW SCHEDULE ARE REFERENCING THE 2014 FBC. THE |
| | CURRENT CODE IS THE 6TH EDITION 2017. UPDATE AS |
| | REQUIRED. SEC. 553 F.S. |
| | |
| | 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL) |
| | |
| | A) OVERHEAD GARAGE DOOR SIZE SPECIFIED ON PLANS. |
| | |
| | B) PEEL AND STICK UNDERLAYMENT FOR SHINGLES AS |
| | SPECIFIED ON SHEET A5. |
| | |
| | 9-DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. VALUATION WAS UPDATED TO $179,848. THE |
| | PERMIT FEE BALANCE IS $3713.47. |
| | |
| | 11- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR |
| | REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW |
| | COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |