| Plan Review Notes For Permit 19010234 |
| Permit Number |
19010234 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-01-28 05:34:14 | 1) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THIS | | | SUBMITTAL. DELETE ALL OLD DRAWINGS AND SUBMIT TWO | | | COMPLETE DRAWINGS FOR REVIEW. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) WHAT STANDARD ARE THE SIZING TABLES FROM? THERE IS | | | NO INFORMATION ON THE SIZING TABLES AS TO WHERE THEY | | | ARE TAKEN FROM. CLARIFY. WPB AMEND, TO FBC SEC. | | | 107.2.1. | | | 3) CLARIFY THE LOCATION OF THE DRYER ON THE PLANS. IS | | | IT LOCATED IN AN OPEN ROOM, CLOSET, ETC.? | | | 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR. 2ND | | | REQUEST.2017 FBC-RES. SEC. G2407.1 AND G2439.4. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|