2019-01-08 15:19:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS AN INDICATON OF AN EXISTING TENANT FIRE
 SEPARATION WALL AND AN INFILL WITHIN THE WALL.
  
 THERE IS NO INDICATION OF A LISTED FIRE WALL DESIGN TO
 MATCH THE PROPOSED INFILL.
  
 PER NFPA 1, CHAPTER 12, FEATURES OF FIRE PROTECTION
  
 12.3 FIRE-RESISTIVE MATERIALS AND CONSTRUCTION.
 12.3.1 THE DESIGN AND CONSTRUCTION OF FIRE WALLS AND
 FIRE BARRIER WALLS
 THAT ARE REQUIRED TO SEPARATE BUILDINGS OR SUBDIVIDE A
 BUILDING TO PREVENT
 THE SPREAD OF FIRE SHALL COMPLY WITH SECTION 12.3 AND
 NFPA 221,
 STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE WALLS, AND
 FIRE BARRIER
 WALLS.
  
 12.3.3* MAINTENANCE OF FIRE-RESISTIVE CONSTRUCTION.
 12.3.3.1 REQUIRED FIRE-RESISTIVE CONSTRUCTION,
 INCLUDING FIRE BARRIERS, FIRE
 WALLS, EXTERIOR WALLS DUE TO LOCATION ON PROPERTY,
 FIRE-RESISTIVE
 REQUIREMENTS BASED ON TYPE OF CONSTRUCTION, DRAFT-STOP
 PARTITIONS, AND
 ROOF COVERINGS, SHALL BE MAINTAINED AND SHALL BE
 PROPERLY REPAIRED,
 RESTORED, OR REPLACED WHERE DAMAGED, ALTERED, BREACHED,
 PENETRATED,
 REMOVED, OR IMPROPERLY INSTALLED.
  
 PLEAE PROVIDE A LISED WALL DESIGN .
  
  
  
  
 2) THERE IS A NEW DOOR INDICATED. THERE IS NO DOOR SIZE
 OR SCHEDULE, INCLUDING HARDWARE, INDICATED.
  
 IF THIS AN EXIT DOOR?
  
 IS THE WALL A RATED WALL?
  
 IF THE WALL IS A RATED WALL, THE DOOR IS REQUIRED TO BE
 RATED.
  
 PLEASE PROVIDE DETAILS
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  