| 2019-03-01 17:22:54 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19010208 |
| | 1/25/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1.0: REFER TO SECTION 514.2 FBC M PROHIBITED |
| | APPLICATIONS: ENERGY RECOVERY VENTILATION SYSTEMS SHALL |
| | NOT BE USED IN THE FOLLOWING SYSTEMS: |
| | 1.HAZARDOUS EXHAUST SYSTEMS COVERED IN SECTION 510. |
| | IT APPEARS THAT THE REVISED PLAN IS NOT IN COMPLIANCE. |
| | |
| | 2) COMMENT #11 FROM THE 1ST REVIEW STILL EXISTS: THE |
| | REQUESTED UL CERTIFICATE FOR THE GENERATOR SHOWING |
| | LISTING AND LABELING IN ACCORDANCE WITH UL 2200 NOT |
| | SUBMITTED- SECTION 915.1 FBC M. PLEASE NOTE THE |
| | GENERATOR SHALL ALOS BE IN COMPLIANCE WITH NFPA 37- |
| | SECTION 915.2 FBC M. |
| | |
| | 3) COMMENT #12 FROM THE 1ST REVIEW STILL EXISTS: SITE |
| | SPECIFIC WIND LOAD ENGINEERING FOR THE GENERATOR |
| | INSTALLATIONS IS REQUIRED- SEE SECTION 1609 FBC B. THE |
| | SUBMITTED WIND LOAD COMMUTATIONS FROM GENERAC ARE BASED |
| | ON THE OUTDATED ASCE 7-98 AND HAVE A DISCLAIMER THAT |
| | STATES THE SUMMARY RESULTS IN THE DOCUMENT ARE FOR |
| | REFERENCE ONLY AND MUST BE VERIFED BY A LICENSED |
| | ENGINEER IN THE STATE OF RECORD. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |