| 2019-01-25 15:35:52 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19010208 |
| | 1/25/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) EXHAUST VENTILATION IS REQUIRED FOR THE UPS SYSTEM, |
| | HOWEVER DETERMINING HOW THE SYSTEM WILL BE VENTILATED |
| | IS DEPENDENT ON SUBMITTAL OF MSDS SHEETS FOR THE |
| | BATERRIES, AND CLARIFICATION OF HOW THE BATTERIES ARE |
| | BEING STORED, AND BATTERY QUANTITIES- SEE FBC M CODE |
| | SECTIONS BELOW. |
| | |
| | 502.4 STATIONARY STORAGE BATTERY SYSTEMS. |
| | STATIONARY STORAGE BATTERY SYSTEMS, AS REGULATED BY THE |
| | FLORIDA FIRE PREVENTION CODE, SHALL BE PROVIDED WITH |
| | VENTILATION IN ACCORDANCE WITH THIS CHAPTER AND SECTION |
| | 502.4.1 OR 502.4.2. |
| | EXCEPTION: LITHIUM-ION AND LITHIUM METAL POLYMER |
| | BATTERIES SHALL NOT REQUIRE ADDITIONAL VENTILATION |
| | BEYOND THAT WHICH WOULD NORMALLY BE REQUIRED FOR HUMAN |
| | OCCUPANCY OF THE SPACE. |
| | |
| | 502.4.1 HYDROGEN LIMIT IN ROOMS. |
| | FOR FLOODED LEAD ACID, FLOODED NICKEL CADMIUM AND VRLA |
| | BATTERIES, THE VENTILATION SYSTEM SHALL BE DESIGNED TO |
| | LIMIT THE MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0 |
| | PERCENT OF THE TOTAL VOLUME OF THE ROOM. |
| | |
| | 502.4.2 VENTILATION RATE IN ROOMS. |
| | CONTINUOUS VENTILATION SHALL BE PROVIDED AT A RATE OF |
| | NOT LESS THAN 1 CUBIC FOOT PER MINUTE PER SQUARE FOOT |
| | (CFM/FT2) [0.00508 M3/(S ? M2)] OF FLOOR AREA OF THE |
| | ROOM. |
| | |
| | 502.4.3 SUPERVISION. |
| | MECHANICAL VENTILATION SYSTEMS REQUIRED BY SECTION |
| | 502.4 SHALL BE SUPERVISED BY AN APPROVED CENTRAL, |
| | PROPRIETARY OR REMOTE STATION SERVICE OR SHALL INITIATE |
| | AN AUDIBLE AND VISUAL SIGNAL AT A CONSTANTLY ATTENDED |
| | ON-SITE LOCATION. |
| | |
| | 502.5 VALVE-REGULATED LEAD-ACID BATTERIES IN CABINETS. |
| | VALVE-REGULATED LEAD-ACID (VRLA) BATTERIES INSTALLED IN |
| | CABINETS, AS REGULATED BY THE FLORIDA FIRE PREVENTION |
| | CODE, SHALL BE PROVIDED WITH VENTILATION IN ACCORDANCE |
| | WITH SECTION 502.5.1 OR 502.5.2. |
| | |
| | 502.5.1 HYDROGEN LIMIT IN CABINETS. |
| | THE CABINET VENTILATION SYSTEM SHALL BE DESIGNED TO |
| | LIMIT THE MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0 |
| | PERCENT OF THE TOTAL VOLUME OF THE CABINET DURING THE |
| | WORST-CASE EVENT OF SIMULTANEOUS BOOST CHARGING OF ALL |
| | BATTERIES IN THE CABINET. |
| | |
| | 502.5.2 VENTILATION RATE IN CABINETS. |
| | CONTINUOUS CABINET VENTILATION SHALL BE PROVIDED AT A |
| | RATE OF NOT LESS THAN 1 CUBIC FOOT PER MINUTE PER |
| | SQUARE FOOT (CFM/FT2) [0.00508 M3/(S ? M2)] OF THE |
| | FLOOR AREA COVERED BY THE CABINET. THE ROOM IN WHICH |
| | THE CABINET IS INSTALLED SHALL BE VENTILATED AS |
| | REQUIRED BY SECTION 502.4.1 OR 502.4.2. |
| | |
| | 502.5.3 SUPERVISION. |
| | MECHANICAL VENTILATION SYSTEMS REQUIRED BY SECTION |
| | 502.5 SHALL BE SUPERVISED BY AN APPROVED CENTRAL, |
| | PROPRIETARY OR REMOTE STATION SERVICE OR SHALL INITIATE |
| | AN AUDIBLE AND VISUAL SIGNAL AT A CONSTANTLY ATTENDED |
| | ON-SITE LOCATION. |
| | |
| | 2) PROVIDE THE FOLLOWING INFORMATION FOR THE UPS |
| | SYSTEMS AS OUTLINED IN SECTION 414.1.3 FBC B. PLEASE |
| | NOTE THAT THE WALLS ENCLOSING THE UPS ROOM MAY HAVE TO |
| | BE FIRE-RATED. |
| | |
| | 414.1.3 INFORMATION REQUIRED. |
| | A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL |
| | IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF |
| | HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED |
| | SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO |
| | SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION |
| | CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE |
| | METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT |
| | NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS |
| | AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE |
| | REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION |
| | AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON, |
| | FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL |
| | AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY. |
| | |
| | 3) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION C403.2.1 FBC EC. |
| | |
| | 4) PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE NEW UPS |
| | ADDITION AND ENCLOSED WALKWAY- SECTION |
| | |
| | 5) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE NEW |
| | UPS ADDITION AND ENCLOSED WALKWAY- TABLE 404.3.1.1 FBC |
| | M. |
| | |
| | 6) SHEET M1.0: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | SUPPLY AIR SYSTEMS OF EACH NEW AC SYSTEM PER SECTION |
| | 606.2.1. PLEASE PROVIDE SYSMBOLS ON THE PLAN AT THE |
| | REQUIRED LOCATIONS, AND INDICATE A SEQUENCE OF |
| | OPERATION FOR FAN SHUTDOWN ON SHEET M2.0- SECTION 606.4 |
| | FBC M. |
| | |
| | 7) M3.0: INDICATE THE TYPE AND SIZE FASTENER TO ATTACH |
| | THE CONDENSER CLIP TO THE CONDENSER HOUSING AND PROVIDE |
| | THE WIND LOAD DESIGN CRITERIA- SECTION 301.15 FBC M AND |
| | SECTION 1609 FBC M. |
| | |
| | 8) PROVIDE A DETAIL SHOWING HOW THE AIR HANDLERS WILL |
| | BE ATTACHED AND SUSPENDED FROM THE STRUCTURE- SECTION |
| | 304.1 FBC M |
| | |
| | 9) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR |
| | HANDLERS- SECTION 307.2.1 FBC M. |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION MANUAL FOR THE GENERATORS- SECTION 304.1 |
| | FBC M.. |
| | |
| | 11) SUBMIT THE UL COMPLIANCE CERTIFICATES FOR THE |
| | GENERATORS- SECTION 915.2 FBC M. |
| | |
| | 12) PROVIDE WIND LOAD ENGINEERING AND DETAILS FOR |
| | INSTALLATION OF THE GENERATORS- SECTION 301.15 FBC M. |
| | |
| | 13) SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR |
| | THE LOUVERS- RULE 9N-3 FAC. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |