Plan Review Notes
Plan Review Notes For Permit 19010181
Permit Number 19010181
Review Stop E
Sequence Number 2
Notes
Date Text
2019-05-02 15:49:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. LOAD CALCULATION USED IS THE TYPE PERMITTED FOR
 RESIDENTIAL CALCULATIONS ONLY. PROVIDE ACCURATE LOAD
 CALCULATION FOR SERVICE, INCLUDE EXISTING AND NEW LOADS
 TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30 (LOAD CALCULATION STILL NOT CORRECT. THE
 FIRST 10,000 VA AT 100% AND THE REMAINDER AT 50%
 CALCULATION CAN ONLY BE USED FOR RECEPTACLE LOADS WHERE
 THE LOAD ON THE RECEPTACLE IS 180 VA EACH. THE OTHER
 EQUIPMENT THAT WAS INCLUDED IN THIS CALCULATION IS NOT
 PERMITTED TO BE INCLUDED IN THE DEMAND FACTOR PORTION.
 THIS EQUIPMENT SHOULD BE ADDED AT 100%. IF CORRECTED
 LOAD CALCULATION EXCEEDS THE RATING OF THE ELECTRICAL
 PANEL OR THE CONDUCTORS SUPPLYING THIS PANEL, PROVIDE
 CORRECTIONS.)
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. SIZE OF
 SERVICE IS NOT CURRENTLY STATED ON PLAN. NEC 215.5; WPB
 FBC 107.2.1 (NOT PROVIDED.)
 3. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  