| 2019-03-13 10:45:42 | PLUMBING 1ST REVIEW**DENIED***3/13/19 |
| | |
| | 1) CITY RECORDS SHOW THE EXISTING BATHROOM UNDER PERMIT |
| | #14110788 ACCESSIBILITY AND DOES NOT HAVE A SHOWER. IT |
| | APPREARS WORK IN THIS SPACE WAS PERFORMED / STARTED |
| | WITH OUT PERMITS AS CITIED ON 12/21/2018 FBC 105.1. THE |
| | RESTOOM WILL HAVE TO FULLY COMPLY WITH CURRENT 2017 6TH |
| | ED FBC-ACCESSIBILITY CODE CHAPTER 6. |
| | |
| | 2) PROVIDE MANUFACTURES SPEC/ INSTALLATION MANUAL FOR |
| | THE WATER HEATER. FBC 107.3.5 |
| | |
| | 3) ANY AND ALL COVERED/ UNPERMITTED WORK SHALL BE |
| | UNCOVERED, TESTED, AND APPROVED BY FIELD INSPECTOR. |
| | |
| | 4) SHT. P1 ISOMETRIC SHOW THE ENTIRE BATHROOM GROUP NOT |
| | VENTED. PER FBC 901.2.1 AND OR DOES NOT MEET FBC 912.1 |
| | HAVE MORE THEN 1 WET VENTED FIXTURE BEYOND THE VENT. |
| | |
| | 5) JOB VALVE. BY THE AMOUNT OF WORK ALREADY DONE AND |
| | NOW WHAT IS REQUIRED THE BUILDING VALUE SEEMS LOW. |
| | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATIONOF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOWDETAILED, QUANTITY |
| | ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING |
| | LAND VALUE) TO MEET THEAPPROVAL OF THE BUILDING |
| | OFFICIAL. FOR PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALLBE TOTAL REPLACEMENT VALUE |
| | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISH,RELATIVE SITE WORK, ARCHITECTURAL AND |
| | DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; |
| | EXCLUDING ONLY LAND VALUE. |
| | |
| | 6) PROVIDE EXISTING & CURRENT OCCUPANCY AND OCCUPANT |
| | LOAD. FBC 107.3.5 |
| | |