| Plan Review Notes For Permit 19010164 |
| Permit Number |
19010164 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-01-10 11:50:31 | 1) THE APPLICATION NOTES THAT THE WATER HEATER IS BEING | | | RELOCATED. SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING | | | THE EXISTING LOCATION AND THE NEW LOCATION OF THE WATER | | | HEATER. THE FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 2) SUBMIT A GAS DRAWING SHOWING THE EXISTING LOCATION | | | OF THE WATER HEATER AND THE PROPOSED NEW LOCATION OF | | | THE WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | | FBC-FUEL GAS CODE SEC.304.1 OR 2017 FBC-RES. SEC.G | | | 2407.1. | | | 4) SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF | | | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE | | | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER | | | 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES. | | | SEC.G2426 THROUGH G2439. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|