Plan Review Notes
Plan Review Notes For Permit 19010144
Permit Number 19010144
Review Stop M
Sequence Number 1
Notes
Date Text
2019-01-09 17:27:481ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010144
 1/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS DO NOT PROVIDE ANY DETAILS AND
 SPECIFICATIONS FOR THE GREASE EXHAUST AND MAKEUP AIR
 DUCTS. PLEASE PROVIDE COMPLETE PLANS- SEXCTION 107.2.1
 WPB.
  
 2) THE PLANS MUST BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL WHO PREPARED THEM, OR BEAR THE SHOP
 DRAWING APPROVAL STAMP OF THE MAIN BUILDING DESIGN
 PROFESSIONAL OF RECORD- SECTIONS 107.1 & 107.2.1 WPB.
  
 3) INDICATE THE TYPE OF HOOD BACKING TO BE USED AND THE
 DIMENSIONS OF THE BACKING- SEE SECTION 507.2.6
 EXCEPTION FBC M.
  
 4) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  