2019-01-08 15:01:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE INSTALLATION SHALL COMPLY WITH NFPA 96.
  
 PER CHAPTER 10, FIRE-EXTINGUISHING EQUIPMENT
  
 10.2.6 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS SHALL BE
 INSTALLED IN
 ACCORDANCE WITH THE TERMS OF THEIR LISTING, THE
 MANUFACTURER?S
 INSTRUCTIONS, AND THE FOLLOWING STANDARDS WHERE
 APPLICABLE:
 (1) NFPA 12
 (2) NFPA 13
 (3) NFPA 17
 (4) NFPA 17A
 (5) NFPA 750
  
 PLEASE ENSURE COMPLIANCE PRIOR TO INSPECTION.
  
  
  
 2) TIE - IN THE FIRE ALARM SYSTEM PER NFPA .
  
 10.6 SYSTEM ANNUNCIATION.
 10.6.1 UPON ACTIVATION OF AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM,
 AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED
 TO
 SHOW THAT THE SYSTEM HAS ACTIVATED.
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCY
 WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE
 ACTIVATION
 OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL
 ACTIVATE
 THE FIRE ALARM SIGNALING SYSTEM.
  
  
  
 3) PROVIDE MANUFACTURER'S EQUIPMENT SPEC SHEETS FOR
 FIRE INSPECTOR REVIEW ON INSPECTION.
  
 ENSURE SPEC SHEETS ARE PROVIDED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  