| 2019-01-08 15:01:31 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) THE INSTALLATION SHALL COMPLY WITH NFPA 96. |
| | |
| | PER CHAPTER 10, FIRE-EXTINGUISHING EQUIPMENT |
| | |
| | 10.2.6 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS SHALL BE |
| | INSTALLED IN |
| | ACCORDANCE WITH THE TERMS OF THEIR LISTING, THE |
| | MANUFACTURER?S |
| | INSTRUCTIONS, AND THE FOLLOWING STANDARDS WHERE |
| | APPLICABLE: |
| | (1) NFPA 12 |
| | (2) NFPA 13 |
| | (3) NFPA 17 |
| | (4) NFPA 17A |
| | (5) NFPA 750 |
| | |
| | PLEASE ENSURE COMPLIANCE PRIOR TO INSPECTION. |
| | |
| | |
| | |
| | 2) TIE - IN THE FIRE ALARM SYSTEM PER NFPA . |
| | |
| | 10.6 SYSTEM ANNUNCIATION. |
| | 10.6.1 UPON ACTIVATION OF AN AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM, |
| | AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED |
| | TO |
| | SHOW THAT THE SYSTEM HAS ACTIVATED. |
| | 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING |
| | THE OCCUPANCY |
| | WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE |
| | ACTIVATION |
| | OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL |
| | ACTIVATE |
| | THE FIRE ALARM SIGNALING SYSTEM. |
| | |
| | |
| | |
| | 3) PROVIDE MANUFACTURER'S EQUIPMENT SPEC SHEETS FOR |
| | FIRE INSPECTOR REVIEW ON INSPECTION. |
| | |
| | ENSURE SPEC SHEETS ARE PROVIDED. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |