Plan Review Notes
Plan Review Notes For Permit 19010142
Permit Number 19010142
Review Stop M
Sequence Number 2
Notes
Date Text
2019-10-02 09:07:562ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19010142
 10/2/19
  
 CODES IN EFFECT:
  
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE COMMENTS LISTED BELOW FROM THE 1ST REVIEW HAVE NOT
 BEEN COMPLETELY RESOLVED.
  
 4) THE PROPERTY IS IN A FLOOD ZONE THEREFORE THE
 CONDENSER SHALL BE INSTALLED ABOVE THE BASE FLOOD
 ELEVATION HEIGHT. PLEASE SEE SECTIONS M1401.5 AND
 R322.1.6 FBC R FOR MORE INFORMATION. (VERIFY THE
 CONDENSER IS MOUNTED AT OR ABOVE BASE FLOOD ELEVATION).
  
 6) THE PROPOSED AC SYSTEM IS PART OF A LARGER SCOPE OF
 WORK WHICH IS CONVERSION OF PORCHES INTO HABITABLE
 LIVING SPACE. ALL PHYSICAL BUILDING DATA LISTED ON THE
 FLORIDA ENERGY EFFICIENCY FORM R405-2017 NEEDS TO BE
 CONFIRMED ON NEW BUILDING PLANS- SECTION 107.2.1 WPB.
 (PROVIDE NEW BUILDING PLANS FOR THE PORCH CONVERSIONS)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  