| 2019-01-14 17:57:07 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19010142 |
| | 1/14/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM- SECTION R403.6 FBC-EC. |
| | |
| | 2) SHOW HOW AIR IS BEING RETURNED TO THE NEW AIR |
| | HANDLER- M1602.3 FBC M. |
| | |
| | 3) PROVIDE A CONDENSATE DISPOSAL PLAN- M1411.3 |
| | |
| | 4) PROVIDE CONSTRUCTION DETAILS FOR INSTALLATION OF THE |
| | NEW EXTERIOR CONDENSER PER SECTION M1401.4 AND |
| | 1305.1.4.1 FBC R. PLEASE NOTE THE PROPERTY IS IN A |
| | FLOOD ZONE THEREFORE THE CONDENSER SHALL BE INSTALLED |
| | ABOVE THE BASE FLOOD ELEVATION HEIGHT. PLEASE SEE |
| | SECTIONS M1401.5 AND R322.1.6 FBC R FOR MORE |
| | INFORMATION. |
| | |
| | 5) PROVIDE AN ELECTRICAL PLAN AND AN ELECTRICAL |
| | SUB-PERMIT- SECTION 107.2.1 WPB. |
| | |
| | 6) THE PROPOSED AC SYSTEM IS PART OF A LARGER SCOPE OF |
| | WORK WHICH IS CONVERSION OF PORCHES INTO HABITABLE |
| | LIVING SPACE. ALL PHYSICAL BUILDING DATA LISTED ON THE |
| | FLORIDA ENERGY EFFICIENCY FORM R405-2017 NEEDS TO BE |
| | CONFIRMED ON NEW BUILDING PLANS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |